Rockwell Automation Publication 1769-UM021G-EN-P - October 2015
173
Use I/O Modules with CompactLogix 5370 L1 Controllers
Chapter 7
5.
On the New Task dialog box, complete the following steps.
a. Name the task.
b. Change the task type to Event.
c. Choose the trigger.
d. Select the tag.
e. If desired, set a time so the Event task executes if no event occurs with
the value.
On the following example dialog box, the time is 10 ms. If no event
occurs for 10 ms, the Event task executes.
f. Set the task priority.
The default Event task priority level is 10. For more information about
Event tasks, see Using Event Tasks with Logix5000 Controllers white
paper,
.
g. Make more desired configuration changes.
h. Click OK.
The new Event task appears in the Controller Organizer.