212
Rockwell Automation Publication 1769-UM021G-EN-P - October 2015
Chapter 8
Use I/O Modules with CompactLogix 5370 L2 Controllers
Analog Input Data Format
lists the bit value combinations you can use to select the output data
format for analog data that is sent to the controller for a channel.
You use bits 8…10
in words 3, 9, 15, and 21 to make this selection.
Analog Input Type and Operating Range
lists the bit value combinations you can use to select the input type and
operating range for a channel.
You use bits 0…5 in words 3, 9, 15, 21, 29, and 37 to
make the selections.
Table 20 - Analog Input Data Format
Analog Output Data Format
Bit Settings
(Words 3, 9, 15, and 21)
Bit 10
Bit 09
Bit 08
Raw/Proportional Data
0
0
0
Engineering Units
0
0
1
Engineering Units x 10
0
1
0
Scaled for PID
0
1
1
Percent Range
1
0
0
Spare
(1)
(1) An attempt to write a non-valid (any Spare value) bit configuration into the Input/Output Data Format Select field causes a Module
Configuration Error (contained in Mod_Condition Array). All bits shown as 0 in
are set to 0.
Values 5
…7
Table 21 - Analog Input Type and Operating Range
Input Type and Normal
Operating Range
Bit Settings
(Words 3, 9, 15, and 21)
Bit 05
Bit 04
Bit 03
Bit 02
Bit
Bit 00
-10
…10V DC
0
0
0
0
0
0
0…5V DC
0
0
0
0
0
1
0…10V DC
0
0
0
0
1
0
4…20 mA
0
0
0
0
1
1
1…5V DC
0
0
0
1
0
0
0…20 mA
0
0
0
1
0
1
-50 mV…50 mv
0
0
0
1
1
0
-100…100 mV
0
0
0
1
1
1
Thermocouple J
0
0
1
0
0
0
Thermocouple K
0
0
1
0
0
1
Thermocouple T
0
0
1
0
1
0
Thermocouple E
0
0
1
0
1
1
Thermocouple R
0
0
1
1
0
0
Thermocouple S
0
0
1
1
0
1
Thermocouple B
0
0
1
1
1
0
Thermocouple N
0
0
1
1
1
1