Rockwell Automation Publication 1756-UM540E-EN-P - December 2017
37
Analog I/O Module Features
Chapter 2
lists the 1756-IT16 module error at 25 °C (77 °F) when using a
thermocouple input type.
Table 6 - 1756-IT16 Module Error At 25 °C (77 °F) with Thermocouple Input Type
(1)
Application
Temperature
Module Error (+/-) at 25 °C (77 °F) When Connected to Thermocouple Types
Type B
Type C
Type D
Type TXK/
XK(L)
Type R
Type S
Type E
Type J
Type K
Type N
Type T
-200 °C (-328 °F)
—
—
—
3.30 °C
—
—
3.58 °C
4.12 °C
5.90 °C
9.06 °C
5.72 °C
0 °C (32 °F)
—
6.92 °C
9.18 °C
1.86 °C
17.02 °C
16.66 °C
1.54 °C
1.78 °C
2.28 °C
3.44 °C
2.32 °C
200 °C (392 °F)
—
5.30 °C
5.66 °C
1.42 °C
10.18 °C
10.64 °C
1.22 °C
1.62 °C
2.26 °C
2.72 °C
1.70 °C
400 °C (752 °F)
22.16 °C
4.74 °C
4.72 °C
1.24 °C
8.68 °C
9.40 °C
1.12 °C
1.64 °C
2.14 °C
2.42 °C
1.46 °C
600 °C (1112 °F)
15.12 °C
4.74 °C
4.44 °C
1.12 °C
7.92 °C
8.82 °C
1.12 °C
1.54 °C
2.12 °C
2.32 °C
—
800 °C (1472 °F)
11.78 °C
4.74 °C
4.40 °C
1.02 °C
7.30 °C
8.28 °C
1.14 °C
1.40 °C
2.20 °C
2.30 °C
—
1000 °C (1832 °F)
9.86 °C
4.74 °C
4.50 °C
—
6.80 °C
7.80 °C
1.20 °C
1.52 °C
2.30 °C
2.34 °C
—
1200 °C (2192 °F)
8.70 °C
5.30 °C
4.72 °C
—
6.46 °C
7.48 °C
—
1.58 °C
2.46 °C
2.42 °C
—
1400 °C (2552 °F)
7.98 °C
5.62 °C
4.94 °C
—
6.36 °C
7.42 °C
—
—
2.66 °C
—
—
1600 °C (2912 °F)
7.70 °C
6.00 °C
5.26 °C
—
6.48 °C
7.60 °C
—
—
—
—
—
1800 °C (3272 °F)
7.84 °C
6.92 °C
5.70 °C
—
7.34 °C
8.72 °C
—
—
—
—
—
2000 °C (3632 °F)
—
7.50 °C
6.38 °C
—
—
—
—
—
—
—
—
2200 °C (3992 °F)
—
8.18 °C
7.90 °C
—
—
—
—
—
—
—
—
(1) This table repr/-.04% typical error while the maximum stated error is +/- 0.10%.
IMPORTANT
When calculating total measurement error, module error at 25 °C (77 °F) is only
one factor in deriving the total measurement error budget.
Other factors that impact thermocouple measurement error include
the following:
•
Thermocouple sensor accuracy/error
•
Conditions of thermocouple wire, such as wire length
•
Cold junction compensation values