Analog I/O Module Tag Definitions
Appendix A
Ch[x]. TempEnglish
BOOL
Used with the TempAbsolute tag for the same channel to
determine the temperature units for the channel when
linearizing (non-zero sensor type).
•
0 = Standard (default)
•
1 = English
IMPORTANT
: The combination of
this value with that of the
TempAbsolute tag value determine
the temperature unit used.
For example, if TempEnglish = 0
and TempAbsolute = 0, the
combination is 00.
Thus, Celsius units are used.
The following combinations are
possible:
•
00 = Celsius
•
01 = Fahrenheit
•
10 = Kelvin
•
11 = Rankine
Ch[x].TempAbsolute
BOOL
Used with the TempEnglish tag for the same channel to
determine the temperature units for the channel when
linearizing (non-zero sensor type).
•
0 = Familiar (default)
•
1 = Absolute
IMPORTANT
: See the TempEnglish
tag Valid Values description for
more information on using this tag’s
value.
Ch[x].DigitalFilter
INT
Determines the time constant for a first order lag filter.
Default = 0 (no filtering).
0…32,767 ms
Ch[x].SensorOffset
REAL
Sensor offset in either temperature units or mV to add
into the input value to compensate for any sensor error in
the system.
Default = 0.0.
Any