196
Rockwell Automation Publication 1756-UM540E-EN-P - December 2017
Appendix A
Analog I/O Module Tag Definitions
1756-IR12 Module Tags
This section describes the tags associated with the 1756-IR12 module.
Configuration Tags
The following table describes the Configuration tags associated with the
1756-IR12module.
IMPORTANT
Each application’s series of tags varies but no input module application
contains any tags that are not listed here.
Table 34 - 1756-IR12 Module - Configuration Tags
Tag Name
Data Type
Definition
Valid Values
Ch[x].InputRange
SINT
Indicates the channel’s operating range.
•
6 = 0…500 Ω
•
7 = 0…1000 Ω
•
8 = 0…2000 Ω
•
9 = 0…4000 Ω
Ch[x].SensorType
SINT
RTD sensor type used on the channel. The Input Type
connected to the channel determine the sensor type
•
0 = Ω
•
1 = 100Ω PT 385
•
2 = 200Ω PT 385
•
3 = 500Ω PT 385
•
4 = 1000Ω PT 385
•
5 = 100Ω PT 3916
•
6 = 200Ω PT 3916
•
7 = 500Ω PT 3916
•
8 = 1000Ω PT 3916
•
9 = 10Ω CU 427
•
10 = 120Ω NI 672
•
11 = 100Ω NI 618
•
12 = 120Ω NI 618
•
13 = 200Ω NI 618
•
14 = 500Ω NI 618
Ch[x].NotchFilter
SINT
Notch Filter removes line noise for the channel.
All channels have the same setting based on Channel 0
For more information on Notch Filter, see
.
Default = 2 (60 Hz)
•
1 = 50 Hz
•
2 = 60 Hz
•
3 = 100 Hz
•
5 = 1000 Hz
•
6 = 20 Hz
•
8 = 500 Hz
•
9 = 5000 Hz
Ch[x].Disable
BOOL
Disables the channel.
B3
•
0 = Enabled (default)
•
1 = Disabled