202
Rockwell Automation Publication 1756-UM540E-EN-P - December 2017
Appendix A
Analog I/O Module Tag Definitions
Input Tags
The following table describes the Input tags associated with the 1756-IT16
module.
Table 37 - 1756-IT16 Module - Input Tags
Tag Name
Data Type
Definition
Valid Values
Fault
DINT
Standard Analog Fault mask – controller sets bottom 16
bits on connection loss.
0000_0000= Connection is good
CIPSyncValid
BOOL
Indicates whether the module is synchronized to a valid
CIP Sync time master on the backplane.
B0 = CIP Sync is not available
CIPSyncTimeout
BOOL
Indicates whether a valid time master on the backplane
has timed out.
B1 = A valid time master was
detected on the backplane, but the
time master has timed out. The
module is currently using its local
clock with old synchronized time
data.
CIPSyncOffsetJump
BOOL
Indicates a significant jump, that is, 1 ms or greater, in the
CST and CIP Sync times sent from the Time Master to the
module. (The Time Master sends the CST and CIP Sync
times to the module every second.)
We recommend that you refresh the Diagnostic Assembly
to get more data on the jump if precise time tracking is
important to your application.
B2
CJ[x].Fault
BOOL
Quality of channel data.
•
0 = Good
•
1 = Bad
CJ[x].Uncertain
BOOL
Channel data can be imperfect.
•
0 = Good
•
1 = Uncertain
CJ[x].Underrange
BOOL
Indicates that Cold Junction Channel x is below 0 °C.
B2
CJ[x].Overrange
BOOL
Indicates that Cold Junction Channel x is above 86 °C.
B3
CJ[0].Data
REAL
Indicates the CJ input data in °C.
Ch[x].Fault
BOOL
Indicates the quality of Input Data.
•
0 = Good
•
1 = Bad
Ch[x].Uncertain
BOOL
Indicates the Input Data can be imperfect.
•
0 = Good
•
1 = Uncertain
Ch[x].Underrange
BOOL
Input is beneath absolute minimum for this channel. If
temperature, set when beneath minimum for that
SensorType.
B2
Ch[x].Overrange
BOOL
Input is above absolute maximum for this channel. If
temperature, set when above maximum for that
SensorType.
B3
Ch[x].CalibrationFault
BOOL
Indicates the last attempted calibration for this channel
failed.
B9
Ch[x].Calibrating
BOOL
Indicates the channel is currently being calibrated.
B10
Ch[x].CalGoodLowRef
BOOL
Indicates that a valid Low Reference signal has been
sampled on this channel.
B11
Ch[x].CalBadLowRef
BOOL
Indicates that an invalid Low Reference signal has been
sampled on this channel.
You must correct this condition to successfully calibrate
the module.
If calibration is aborted with an invalid Low Reference
signal, the
I.Ch[x].CalibrationFault
tag is set for this
channel until a successful calibration is performed.
B12