The back of the boiler and connections are shown in Fig. 4 where: 

 

Figure 1 
- Item 1 is an R1" connection with an outer thread for the flow pipe,  
- Item 2 is an R 1" connection with an outer thread for the return pipe,   
- Item 3 is an R1/2" connection with an inner thread for installation of the thermal valve safety pipe,  
- Item 4 is an R1/2" connection with an inner thread for safety valve installation.   

 

7.1.

 

FLOW PIPE AND RETURN PIPE (Fig. 4, Items 1 and 2 and Fig. 7 and 8, Items 3 

and 10) 

The size of the flow pipe and return pipe outlets is 1" and may not be reduced or tapered before the first branch. Use 1" 

steel pipe or copper pipe of outer diameter Ø 28 mm (or larger diameter). 

While  installing  the  system,  absolutely  make  sure  that  pipe  slopes  are  0.5%  (5  mm  of  pipe  length)  and  that  the  air  is 

released from the system (from the boiler, pipes, radiators). 

You can install a combination temperature and pressure gauge on the flow pipe, although both thermometer and pressure 

gauge are installed at the front of the stove. 

On  the  return  pipe,  install  a  by-pass  line  with  a  pump,  expansion  vessel  and  a  spigot  for  filling  up  and  emptying  the 

system. When you install the pump, take note of the pump’s direction.  

Note: 
Only install the by-pass line if there are conditions for gravity heating. 
 

7.2.

 

THERMAL VALVE WITH BUILT-IN THERMAL PROTECTION AND ADDITIONAL 

ELEMENTS FOR CONNECTION 

To install thermal valve it is necessary to purchase and install: 
1. Thermal valve with built-in thermal protection type 544, 1/2", product Caleffi (Fig. 7a) and Fig. 7, Item 13. 
2. Slope pressure regulator with manometer 1/2", the same or similar as shown in Fig. 7b and Fig. 7, Item 19. 
3. Filter for cold water at the input of the water supply to the thermal valve, Fig. 7, Item 20 
4. Filter for hot - boiling water intake of the boiler and water outlet of thermal valve, Fig. 7, Item 21. 
 

Note: 

These components are not included with product for central heating you bought! 
Installation of thermal valve with built-in thermal protection (Fig. 7, Item 13 and Fig. 7a) with additional elements ensuring 

safe operation, such as pressure regulator (Fig. 7, Item 19 and Fig. 7b). Water filter on the boiler intake (Fig. 7, item 20) and 
water filter on the boiler outlet in closed central heating system is MANDATORY.   This specially refers to a closed system, 
when  the  radiators  are  submerged  and  where  in  case  of  termination  of  the  pump  operation  for  any  reason,  the  water 
temperature in the boiler rapidly increases and overheating occurs very quickly.  

In the open central heating system, installation of thermal fuse is not mandatory.  

 

7.2.1.

 

THERMAL VALVE WITH BUILT-IN THERMAL PROTECTION (Fig. 7, Item 13 and Fig. 7a) 

Thermal fuse is installed near the stove, depending on the available space. It can be installed in any position. You should 

take into account the direction of cold water intake and hot water outlet from the boiler which is clearly marked on the valve 
body.   

The thermal fuse probe (Fig. 7, Item 22) is best to place in the thermal valve connection (Fig. 7, Item 18). It can be placed 

on the discharge - distribution pipe (Fig. 7, Item 3) but at a distance from the boiler of 500 mm the most or at the highest point 
of the boiler before the exhaust pipes. 

Seal it with hemp or other sealing material by tightening.  
Fig. 7 shows the thermal valve installation diagram. 

Summary of Contents for ALFA TERM -27

Page 1: ...ALFA TERM 27 This product meets the requirements of the Ecodesign Directive in terms of efficiency and air pollution level in order to contribute to the reduction of energy consumption and negative en...

Page 2: ...eating power is shown for stoking dry beech wood with lower heating power Hd 4255W kg DEAR BUYERS Thank You for the trust you showed us buying our stove for floor heating We assure You that You have c...

Page 3: ...2 1 THERMAL VALVE WITH BUILT IN THERMAL PROTECTION Fig 7 Item 13 and Fig 7a 7 7 2 2 SLOPE PRESSURE REGULATOR 1 2 WITH MANOMETER Fig 7 Item 19 and Fig 7b 8 7 2 3 WATER FILTER OF THE BOILER INTAKE Fig...

Page 4: ...CKAGING MAY CAUSE SUFFOCATION THESE INCLUDE PLASTIC BAGS FILMS STYROFOAM ETC 2 3 THE RESPONSIBILITY OF THE INSTALLER The responsibility of the installer is to perform all the checkups of the flue pipi...

Page 5: ...Secondary air regulator knob 19 Ash pan door 10 Thermostat combustion regulator knob 12 Ash pan ash box 13 Grate holder 14 Wood box 15 Cleaning access plate 16 Pressure gauge 17 Thermometer 18 Cooktop...

Page 6: ...inet is mounted above the stove minimum clearance between the stove s cooktop and the cabinet should be at least 40 cm Combustible materials e g wallpapers door casings doors etc require a clearance t...

Page 7: ...box and screw it on the outlet on the cooktop or on the side outlet First remove the cover and use the same screws to fasten the collar NOTE If your chimney is of unsatisfactory or dubious quality we...

Page 8: ...is built on the outside walls it must be well insulated If the chimney connection is tightly connected to the chimney if the connection is extended If it is properly cleaned and free of birds nests di...

Page 9: ...ney pipes that have a rectangular internal cross section with a ratio that differs from the plan Modest efficiency 40 Chimney positioning and distance 7 INSTALLING THE STOVE IN THE WATER HEATING SYSTE...

Page 10: ...ssure regulator with manometer 1 2 the same or similar as shown in Fig 7b and Fig 7 Item 19 3 Filter for cold water at the input of the water supply to the thermal valve Fig 7 Item 20 4 Filter for hot...

Page 11: ...the hot boiling water from dirt and solid objects that can damage the tap seals or seals of the thermal valve This filter must be resistant to water temperatures up to 150 C NOTES After the completio...

Page 12: ...losed expansion vessel 7 Contact thermostat Note It is mandatory to install a thermal discharge valve with thermal protection the so called thermal fuse in accordance with the recommendations from the...

Page 13: ...ected to the chimney as described in the foregoing items NOTE The stove may not be used without water It must be connected to the system which is connected to consumers radiators with the power of no...

Page 14: ...d using the thermostat power regulator combustion regulator which is located in the ash pan door and which automatically sets the regulator damper depending on the regulation knob setting Fig 1 Items...

Page 15: ...odors the next time you heat the oven Clean the cooktop occasionally using fine sandpaper and in the event of longer breaks apply acid free oil on the cooktop vegetable oil Remove burnt material from...

Page 16: ...t If water is leaking from the valve replace the expansion vessel If only air comes out from the valve remove the installation vessel and pump it The pressure in the vessel must be equal to or greater...

Page 17: ...small number of radiators are switched on Transfer the grate to upper position or switch on some other radiator Keep the ashtray door closed 14 Water condensate in the boiler Damp heating material Cha...

Page 18: ...ate of undesirable objects 18 Outline dimensions of ALFA TERM 27 stove Figure 16 19 DETERMINING THE REQUIRED HEAT OUTPUT There is no absolute rule that would allow the calculation of the required heat...

Page 19: ...eating close the air inlet covers and DO NOT open the fireplace door Extinguish the fire with appropriate means home fire extinguisher NEVER USE WATER TO EXTINGUISH THE FIRE Also notify local firefigh...

Reviews: