ZONE ANNUNCIATOR/ CONTROLLER 

MODEL ZAC-32 

INSTALLATION INSTRUCTIONS 

 

I. INTRODUCTION 

 

THE ZAC-32 ZONE ANNUNCIATOR/ CONTROLLER IS A TWO COMPONENT SYSTEM 
COMPRISED OF A CENTRAL ZONE PROCESSOR AND A REMOTE DISPLAY/CONSOLE. THE 
SYSTEM PROVIDES TOTAL ZONE MONITORING AND CONTROL AT A FULL FEATURED REMOTE 
DISPLAY CONSOLE.  

 

THE SYSTEM IS CAPABLE OF ZONE EXPANSION IN THIRTY- TWO ZONE MULTIPLES, AN 
OPTIONAL REMOTE PRINTER PROVIDES A HARD COPY OF ALL ZONE ACTIVITY BY AN 
IDENTIFYING AUTHORIZED CODE NUMBER IN ADDITION TO TIME AND DATE. 

 

THE REMOTE CONSOLE 

 

THE REMOTE CONSOLE CONTROLS AND DISPLAYS ALL THIRTY-TWO ZONES.  THE 
CONDITION OF EACH ZONE IS CLEARLY DISPLAYED ON THE FUNCTIONALLY DESIGNED 
CONSOLE. THE DIGITAL KEYPAD IS USED TO ALLOW AUTHORIZED PERSONNEL ACCESS TO 
THE SYSTEM BY AN IDENTIFYING ACCESS CODE AND TO PERFORM VARIOUS SYSTEM 
FUNCTIONS. 

 

ALL ZONE DATA AND ZONE CONTROL FUNCTIONS ARE TRANSMITTED TO THE ZONE 
PROCESSOR FROM THE REMOTE CONSOLE OVER A FOUR-CONDUCTOR CABLE.  UP TO 
FOUR REMOTE CONSOLES CAN BE ADDED TO THE SYSTEM FOR ANNUNCIATION AND 
CONTROL AT MULTIPLE LOCATIONS.  REMOTE CONSOLES CAN BE LOCATED IN EXCESS OF 
1000 FEET FROM THE ZONE PROCESSOR.  

 

THE ZONE PROCESSOR CABINET  

 

THE ZONE PROCESSOR CABINET CONTAINS THE SYSTEM LOGIC CIRCUITRY, POWER 
SUPPLY AND STANDBY POWER SOURCE.  ALL FIELD WIRING IS TERMINATED IN THE ZONE 
PROCESSOR CABINET.  A FOUR CONDUCTROR CABLE CONNECTS THE ZONE PROCESSOR 
TO THE REMOTE CONSOLE.   
 

     

II.    SYSTEM FEATURES 

 

  

32 ZONES CAN BE WIRED NORMALLY- 

FOUR WIRE REMOTE ANNUNCIATOR 

 

OPEN OR NORMALLY-CLOSED 

DISPLAY CONSOLE 

 

 

 

UP TO FOUR REMOTE CONSOLES 

DIGITAL KEYPAD FOR SYSTEM SECURITY 

 

CAN BE ADDED TO A SYSTEM 

 
 

BUILT-IN AUDIBLE SIGNAL, 80 Db @ 3 FT. 

FOUR SYSTEM FUNCTION INDICATORS 

 
 

THIRTY-TWO ZONE STATUS INDICATORS 

POWER FAILURE AND LOW BATTERY  

  

INDICATION 

 
 

OPTIONAL PRINTER FOR COMPLETE 

OPTIONAL SUPERVISED ZONE MODULE 

 

RECORD OF SYSTEM ACTIVITY 

 
 

OPTIONAL THIRTY-TWO ZONE VOLTAGE 

OPTIONAL EIGHT ZONE RELAY MODULE  

 OUTPUT 

MODULE 

 
 
 

SIXTEEN FOUR DIGIT ACCESS CODES 

 

COMMON ANNUNICATOR VOLTAGE  

  

 

OUPUT 

 

 

 

                                                         

PAGE 1 

Summary of Contents for ZAC-32

Page 1: ...A SYSTEM CONTROL CABINET CONNECTED TO CONSOLE WITH FOUR WIRE CABLE REMOTE CONSOLE CAN BE LOCATED UP TO 1000 FEET FROM CONTROL CABINET BUILT IN AUDIBLE SIGNAL SOUND LEVEL IS 80dB 3 FEET SIXTEEN FOUR DI...

Page 2: ...DUCTOR WIRE DESKTOP ANNUNCIATOR CONECTED TO CABINET WITH 22 GA SHEILDED 4 CONDUCTOR WIRE DESKTOP ANNUNCIATOR SIZE 16 2 L x 8 W x 2 8 D CABINET SIZE 13 H x 11 75 W x 3 5 D RACK MOUNTED ANNUNCIATOR STAN...

Page 3: ...MENTS 2 AC POWER 2 STANDBY BATTERY 2 EARTH GROUND 2 ZONE INPUTS ZAC 32 2 ZONE INPUTS ZAC 32S 3 ZONE TERMINAL DESIGNATIONS 3 CONNECTING PROCESSOR TO PRINTER INTERFACE 4 AUXILIARY VOLTAGE OUTPUTS 4 EXTE...

Page 4: ...NE PROCESSOR FROM THE REMOTE CONSOLE OVER A FOUR CONDUCTOR CABLE UP TO FOUR REMOTE CONSOLES CAN BE ADDED TO THE SYSTEM FOR ANNUNCIATION AND CONTROL AT MULTIPLE LOCATIONS REMOTE CONSOLES CAN BE LOCATED...

Page 5: ...HAVE STANDBY POWER IF FUSE IS BLOWN THE BATTERY FUSE IS LOCATED TO THE RIGHT OF TERMINAL 7 ON THE PRINTED CIRCUIT BOARD C EARTH GROUND THIS UNIT HAS EFFECTIVE LIGHTNING PROTECTION ONLY WHEN GROUNDED A...

Page 6: ...ATION 1 19 21 20 21 _ _ _ _ _ _ _ _ 17 43 45 44 45 _ _ _ _ _ _ _ _ 2 19 22 20 22 _ _ _ _ _ _ _ _ 18 43 46 44 46 _ _ _ _ _ _ _ _ 3 19 23 20 23 _ _ _ _ _ _ _ _ 19 43 47 44 47 _ _ _ _ _ _ _ _ 4 19 24 20...

Page 7: ...AXIMUM TOTAL CURRENT AVAILABLE FROM THESE OUTPUTS IS 700 MA THIS TOTAL OF ALL OUTPUTS SHOULD NOT BE EXCEEDED USE THE PROVIDED CHART TO TOTAL THE SUM OF THE OUTPUTS VOLTAGE OUTPUT TERMINALS CURRENT USE...

Page 8: ...CALCULATING THE TOTAL CURRENT USED BY THE SYSTEM THE REMOTE CONSOLE IS TERMINATED WITH AN EIGHT CONDUCTOR MODULAR CORD AN EIGHT CONDUCTOR MODULAR JACK IS SUPPLIED TO TERMINATE THE CABLE RUN BETWEEN TH...

Page 9: ...C 28 MA NOTE TOTAL CURRENT FROM ALL OUTPUTS NOT TO EXCEED 800 MA FUSES BATTERY FUSE 2 5 SB 3 AG AUXILIARY POWER FUSES 5 x 20MM 500MA ZONE PARAMETERS LOOP RESPONSE TIME 250 MS TO ACTIVATE 125 MS TO RE...

Page 10: ...PREPARED BY THE FEDERAL COMMUNICATION COMMISSION HELPFUL HOW TO IDENTIFY AND RESOLVE RADIO TV INTERFERENCE PROBLEMS THIS BOOKLET IS AVAILABLE FROM THE U S GOVERNMENT PRINTING OFFICE WASHINGTON DC 204...

Page 11: ......

Page 12: ...PLAY CONSOLE THE REMOTE CONSOLE DISPLAYS AND CONTROLS ZONE STATUS AND SYSTEM CONDITIONS THE CONSOLE CONTAINS A DIGITAL KEYPAD ZONE SYSTEM INDICATORS AND AN AUDIBLE SIGNAL A DIGITAL KEYPAD THE DIGITAL...

Page 13: ...THE AUDIBLE ANNUNCIATOR IS NOT RESET THE AUDIBLE SIGNAL WILL SOUND AFTER THE LAST KEY IS PRESSED D MEMORY RESET WHEN A ZONE HAS BEEN VIOLATED THE ZONE MEMORY IS SET IN ORDER TO MONITOR THE ZONE STATU...

Page 14: ...ZONE 2 INDICATOR WILL FLASH BYPASS STATUS OUTPUT WILL TURN ON THE FOLLOWING IS AN EXAMPLE OF THE ZONE UN BYPASS FUNCTION TO UN BYPASS ZONE NUMBER 30 1 LOAD A VALID FOUR DIGIT ACCESS CODE THEN PRESS PO...

Page 15: ...ODE 01 1865 02 9506 03 5198 04 7357 05 9274 06 4742 07 2645 08 2405 09 7928 10 9258 11 8296 12 8320 13 9078 14 9536 15 8878 16 4530 B ZONE DESIGNATIONS STANDARD ZONES 1 24 DAY ZONES 25 32 ALARM CONTRO...

Reviews: