PARAMETER P00 – SELECTS THE MODEL OF BOILER
6. Use buttons ‘+’ and ‘-‘ to modify the value of the parameter:
00 = 20 Kw (default for SRD 20)
01 = 27 Kw (default for SRD 27)
02 = 29 Kw
03 = 36 Kw (default for SRD 36)
04 = 50 Kw
7. Press and release button ‘S’ to con
fi
rm. The parameter
number (P00) will appear on the display.
8. Switch off the appliance and switch it back on again to render
the new parameter operative.
PARAMETER P01 – SELECTS THE TYPE OF BOILER
6. Use buttons ‘+’ and ‘-‘ to modify the value of the parameter:
00 = instantaneous boiler (default)
01 = storage boiler
02 = boiler with storage tank Comfort (+7°C)
7. Press and release button ‘S’ to con
fi
rm. The parameter
number (P01) will appear on the display.
8. Switch off the appliance and switch it back on again to render
the new parameter operative.
PARAMETER P02 – SELECTS THE TYPE OF GAS
6. Use buttons ‘+’ and ‘-‘ to modify the value of the parameter:
00 = Natural Gas (default)
01 = LPG
7. Press and release button ‘S’ to con
fi
rm. The parameter
number (P02) will appear on the display.
8. Switch off the appliance and switch it back on again to render
the new parameter operative.
PARAMETER P03 – SETS THE CENTRAL HEATING TEM-
PERATURE
6. Use buttons ‘+’ and ‘-‘ to modify the value of the parameter:
00 = standard (30-80°C)
01 = reduced (25-40°C) for under-
fl
oor heating.
7. Press and release button ‘S’ to con
fi
rm. The parameter
number (P03) will appear on the display.
8. Switch off the appliance and switch it back on again to render
the new parameter operative.