PARAMETER P14 – IGNITION SEQUENCE SETTING
6. Use buttons ‘+’ and ‘-’ to modify the value of the parameter
between:
min = 33 Hz; max = 203 Hz.
The default value is adjusted according to the output set in pa-
rameter P00.
7. Press and release button ‘S’ to con
fi
rm. The parameter number
(P14) will appear on the display.
8. Switch off the appliance and switch it back on again to render
the new parameter operative.
PARAMETER P15 – ZONE MANAGEMENT BOARD ACTIVATION
6. If the system is
fi
tted with zone valves, set the parameter at ‘01’. If
a remote control is installed, an extra interface board must be in-
stalled to control the zone valves. Then set the parameter at ‘01’.
7. Press and release button ‘S’ to con
fi
rm. The parameter number
(P15) will appear on the display.
8. Switch off the appliance and switch it back on again to render the
new parameter operative.
PARAMETER P16 – TELEPHONE CONTROL ACTIVATION
6. If a telephone interface is installed, enable the board by setting
parameter P16 at ‘01’.
7. Press and release button ‘S’ to con
fi
rm. The parameter number
(P16) will appear on the display.
8. Switch off the appliance and switch it back on again to render
the new parameter operative.
N.B.: The connection of the telephone interface to contact TA of
the terminal board must be wired in parallel with the remote con-
trol using two non-polarised conductors.
PARAMETER P17 – FAN FREQUENCY VALUE DISPLAY
6. Use buttons ‘+’ and ‘-’ to modify the value of the parameter
between:
- 00 = Off;
- 01 = On.
If parameter value 01 is selected, during the boiler operation,
the display will show the fan frequency value for 10 min.
7. Press and release button ‘S’ to con
fi
rm. The parameter number
(P17) will appear on the display.
8. Switch off the appliance and switch it back on again to render
the new parameter operative.
P 15
S
S
S
S
P 16
P 14
S
S
S
S
P 17