Subject to changes in line with technical progress.
25
3061955
Operation
object-name
object-type
object-instance
description ENG
TrendObj25
20
25
TrendObj26
20
26
TrendObj27
20
27
TrendObj28
20
28
TrendObj29
20
29
TrendObj30
20
30
BMSAlmAck
3
30029
BMS Alm ack
Inlettemperature
0
36600
Feed temp.
Returntemperature
0
26206
Return temp.
Soleflowvolumelpm
0
11049
Fluid volume
pressure1
0
28519
Eff. pressure 1
pressure2
0
24324
Eff. pressure 2
Inlettemperatureafterinfeed
0
54992
Temp. After feed
extract exchanger 1
3
63397
Operate coil 1
extract exchanger 2
3
44789
Operate coil 2
extract exchanger 3
3
39365
Operate coil 3
Solelowpressurewarning
3
62468
Warning fluid pressure
SolelowpressureAlarm
3
34533
Alarm fluid pressure
Nosoleflow
3
37994
Fluid flow
Pump1alarm
3
37430
Alarm pump 1
Pump2alarm
3
2538
Alarm pump 2
Soleflowvolumeqm
2
12675
Fluid volume
frostcontroler
2
22201
Frost valve
Frostvalve
1
500
defrost valve
Operatingmode
19
39944
Operating mode
Airvolume1
2
24709
Air volume P1
Airvolume2
2
20710
Air volume P2
Summaryairvolume
2
26578
Sum. air volume
actualsignaloptimazing
2
1087
Opt_Ctrl.PrVal
CmdPump1
4
4295
Pump 1
Pump1
1
35056
Demand pump 1
CmdPump2
4
51269
Pump 2
Pump2
1
26146
Demand pump 2
Powervalve
1
25280
Power ctr. valve
Cmdsource
19
45287
Demand source
DemandBMS
19
39795
BMS release
Externaldemand
19
54661
Ext. demand
DemandDisplay
2
11145
Demand
Optimazing
19
35330
Optimizing
leadingPumpsignal
2
21693
Signal pump
Aktivpump
19
27914
Number of pumps
Globalalarm
4
41370
Central alarm
Warning
4
50808
Warning
State
4
9161
Operating mode
Htgrecovery
2
33917
Htg. power over air
Clg
2
32980
Cool. power over air
Recovery
2
23344
Sum energy