Translation of the original installation and operating instructions
22
AL-KO HYDROOPT
®
Name
Range
Explanation
MB type
None
Slave
No connection via Modbus
HYDROOPT M controller as slave for a higher-level controller
Address
0…247
Address of the HYDROOPT M controller
MB ComType
RTU Int
TCP/IP
Modbus RTU (via serial RS485 interface)
Modbus TCP/IP (via the IP network)
Baud rate
2400
4800
9600
19200
38400
Baud rate for communication in the Modbus system
(Modbus RTU only)
Parity
Parity for communication in the Modbus system (Modbus RTU
only)
Stop bits
Number of stop bits for communication in the Modbus system
(Modbus RTU only)
Termination
Passive
Active
Terminal resistance at the serial interface in the controller deacti-
vated
Terminal resistance at the serial interface activated in the controller
Restart required!
Execute
After changes have been made to the parameters, the controller
must be restarted with Execute to accept the data.
If the Modbus connection is used via the IP network, network settings can be found under the following menu item:
Main menu (press the INFO key) > System integrator > IP Config
Name
Range
Explanation
DHCP
Active
Passive
Setting the type of address reference:
Obtain the address from the DHCP server.
Permanently set IP address.
Current IP
Display of the controller IP address
Curr. mask
Display of the subnet mask
Curr. gateway
Display of the gateway address
Set IP
XXX.XXX.XXX.XXX
Entry of the controller IP address if DHCP is set to passive
Set mask
XXX.XXX.XXX.XXX
Entry of the subnet mask
Set gateway
XXX.XXX.XXX.XXX
Entry of the gateway address
Primary DNS
XXX.XXX.XXX.XXX
Entry of the primary DNS server
Secondary DNS
XXX.XXX.XXX.XXX
Entry of the secondary DNS server
Name
Display of the controller name
MAC
Display of the controller MAC address.
Link
Active
Passive
No connection to Ethernet.
Connection to Ethernet.
100 Mbit
Active
Passive
Switching the transmission speed:
10 Mbit
100 Mbit
Advanced
Change the access data (user names, passwords)
After changing values
Restart required!
Execute
After changes have been made to the parameters, the controller
must be restarted with Execute to accept the data.
Access
Address
Description ENG
Data Type
Unit Value
Input Status
Read-Only for BMS
1x0001
ext. demand
Bit
0 = Off
1 = On
Input Status
Read-Only for BMS
1x0002
Operating mode
Bit
0 = Off
1 = On
Input Status
Read-Only for BMS
1x0003
Pump 1
Bit
0 = Off
1 = On