5.1.2.- PROPORTIONAL BAND (COND_4=1):
Five operating zones are defined.
Pcond (bar)
Tcond (ºC)
POSITIVE FAST ZONE
POSITIVE SLOW ZONE
NEGATIVE SLOW ZONE
NEGATIVE FAST ZONE
The parameters which delimit each of the 5 zones (
COND_5, COND_6, COND_7 and COND_8
) are defined in
bar
or
ºC
according to the parameter
CONF_8
(only in
bar
in the case that CONF_7 = GENERIC).
The
PROPORTIONAL BAND
is divided into as many levels as there are fans in the installation. These levels
determine the start or stop points for the fans.
COND_7
COND_5
COND_1 (COND SP)
COND_6
COND_8