According to CONF_8 parameter
According to CONF_8 parameter
55
Parameter:
Lower limit Evap. SP
Code:
EVAP_3
Units:
Description:
Minimum value permitted for
parameter EVAP_1.
EVAP_2
EVAP_1
EVAP_3
Upper variation margin
Lower variation margin
Parameter:
Compressor Rotation
Code:
EVAP_4
Description:
Type of compressor rotation.
DUOControl
controllers have 2 algorithms implemented for selecting the compressors to
start and/or stop.
OPERATING HOURS:
Always starts the available compressor with the least accumulated
operating time and always stops the compressor with the most accumulated operating
time.
SEQUENTIAL:
The order in which the compressors are started/stopped is set by the
connection to the
DUOControl.
For further information, see
Chapter 4.
Parameter:
Compressor Control
Code:
EVAP_5
Description:
To define the algorithm used to control the compressors.
NEUTRAL ZONE
PROPORTIONAL BAND
For further information, see
Chapter 4.
Parameter:
Positive Differential Slow Zone
Code:
EVAP_6
Units:
Description:
Bandwidth of the POSITIVE SLOW ZONE used in the definition of the algorithms
for controlling the compressors.
For further information, see
Chapter 4.
According to CONF_8 parameter
Parameter:
Negative Differential Slow Zone
Code:
EVAP_7
Units:
Description:
Bandwidth of the NEGATIVE SLOW ZONE used in the definition of the algorithms
for controlling the compressors.
For further information, see
Chapter 4.