67
Parameter:
Fan Safety Circuit
Code:
ENTR_4
Description:
Type of safety circuit for the fans.
Open contact error:
The safety circuit for the fans is closed in normal operation
Normal operation:
+24 V in the input terminals for the fan safety circuits
Safety circuit activated:
0 V in the input terminals for the fan safety circuits
Closed contact error:
The safety circuit for the fans is open in normal operation
Normal operation:
0 V in the input terminals for the fan safety circuits
Safety circuit activated:
+24 V in the input terminals for the fan safety circuits
T-V1
T-V1
IMPORTANT:
The
8
icon indicates that the data is being saved. If the equipment is disconnected
or the power supply fails while this icon is showing, the equipment will return to the last saved
configuration.