52
Compressor
0 VDC
24 VDC
24 VDC
24 VDC
24 VDC
Stages ON
0 of 4
1 of 4
2 of 4
3 of 4
4 of 4
Partial loading-a
0 VDC
0 VDC
24 VDC
24 VDC
24 VDC
Partial loading-b
0 VDC
0 VDC
0 VDC
24 VDC
24 VDC
Partial loading-c
0 VDC
0 VDC
0 VDC
0 VDC
24 VDC
For a compressor with 3 partial loadings:
Compressor
0 VDC
24 VDC
24 VDC
24 VDC
24 VDC
Stages ON
0 of 4
1 of 4
2 of 4
3 of 4
4 of 4
Partial loading-a
24 VDC
24 VDC
0 VDC
0 VDC
0 VDC
Partial loading-b
24 VDC
24 VDC
24 VDC
0 VDC
0 VDC
Partial loading-c
24 VDC
24 VDC
24 VDC
24 VDC
0 VDC
Active when not powered
Active when powered
Parameter:
Alarm Output Activated
Code:
CONF_4
Description:
Notifies whether it has been possible to use a controller terminal as an alarm output.
Section 2.3.2.
shows in which cases this functionality is not available.
Parameter:
Fan Control Type
Code:
CONF_5
Description:
Type of condenser fan control
ON/OFF:
ALL/NOTHING control
INVERTER:
INVERTER control
Parameter:
No. of Fans
Code:
CONF_6
Description:
Number of condenser fans
Modification of this parameter is only permitted by means of the Programming Assistant.