1662H411 Ed.06
23
23
Description
Values Min.
Def.
Max.
dLg
L1
Log interval
0
=1 min.
1
=5 min.
2
=15 min.
3
=30 min.
4
=60 min.
0
2
4
L2
Delete record and event log
0
=No
1
=Yes
0
0
1
l3
Record start day
0
=Monday
1
=Tuesday
2
=Wednesday
3
=Thursday
4
=Friday
5
=Saturday
6
=Sunday
0
0
6
l4
Decimal separator for the .cvs file
0
=,
1
=.
0
0
1
EP
Exit to level 1
Logger (Only with CAMM module)
English
Description
Values Min.
Def.
Max.
In0
O10
Configuration of relay AUX2
0
=Deactivated
1
=Alarm
2
=Light
3
=Virtual control
4
=Solenoid for Hot Gas
0
*
4
o20
Configuración del relé AUX3
0
=Desactivado
1
=Heat resistor
2
=Dehumidifier
0
*
2
o80
Configuration of DEF relay
0
=Deactivated
1
=Extractor fan
2
=Defrost
0
*
2
o81
HUMID. relay configuration
0
=Deactivated
1
=Extractor fan
2
=Humidifier
0
*
2
o90
Analogue output type (AN. OUT)
0
=4-20 mA
1
=0-10 V
0
0
1
o91
P proportional constant of analogue output
1
20
100
o92
I integral constant of analogue output
1
5
200
EP
Exit to level 1
Level 1
Level 2
Inputs and outputs
†
Description
Values Min.
Def.
Max.
KCP
h1
Maximum temperature of HACCP alarm
ºC/ºF
-50
99
99
h2
Maximum permitted time for activation of the HACCP alarm (
0
=Disabled)
H.
0
0
255
EP
Exit to level 1
Level 1
Level 1
Level 2
Level 2
HACCP alarm
* According to wizard.
It can only be modified using the configuration wizard (In1/2).
†