1662H411 Ed.06
19
19
Description
Values Min.
Def.
Max.
RE
SPt
Temperature setting (Set Point)
ºC/ºF
-50
9.0
99
C0
Probe 1 calibration (Offset)
ºC/ºF
-5.0
0.0
5.0
C1
Probe 1 differential (Hysteresis)
ºC/ºF
0.2
2.0
20.0
C2
Set Point top locking (it cannot be set above this value)
ºC/ºF
C3
20
99
C3
Set Point bottom locking (it cannot be set below this value)
ºC/ºF
-50
0
C2
C4
Type of delay for the protection of the compressor:
0
=Minimum time of compressor in OFF
1
=Minimum time of compressor in OFF and in ON in each cycle
0
0
1
C5
Protection delay time (Value of the option selected in parameter C4)
Min.
0
0
120
C6
COOL relay status with fault in probe 1:
0
=OFF;
1
=ON;
2
=ON-OFF according to prog. C7 and C8
0
0
2
C7
Relay time in ON in the event of probe 1 failure
(If C7=0 and C8
¹
0, the relay will always be disconnected in OFF)
Min.
0
10
120
C8
Relay time in OFF in the event of probe 1 failure
(If C8=0 and C7
¹
0, the relay will always be connected in ON)
Min.
0
5
120
C19
Maximum start time from Pump Down
(Values between 1 and 9 seconds will not be accepted) (
0
=deactivated)
Sec.
0
0
120
C20
Maximum time for pump down (
0
= deactivated)
Min.
0
0
15
C21
Probe to be viewed in the upper line of the display
0
=All probes (sequential)
1
=Probe 1 (Chamber)
2
=Probe 2 (Evaporator)
3
=Probe 3 (According to
I30
)
0
1
3
C22
Stop fans and compressor on opening door
0
=No
1
=Yes
0
0
1
C23
Start-up delay for fans and compressor with door open
Min.
0
0
999
C26
Probe 3 calibration (Offset)
ºC/ºF
-20.0
0.0
20.0
Configuration
Condensed programming menu
Enables the rapid configuration of the most frequently-used parameters (
SPt, C1, SPH, rH01, d0, d1, d4, F3, A1,
A2, A21
and
A22
). Press the
SET
key for 3 seconds to access it.
Extended programming menu
Use the extended programming menu to configure all of the unit’s parameters in order to adapt it to installation
requirements. Press the
SET
key for 6 seconds to access it.
IMPORTANT:
If the function of the password has been configured as a keypad block (
b10
=2), or as
an access block to parameters (
b10
=1), you will be requested to enter the access code programmed in
PAS
when attempting to access either of the two functions. If the entered password is not correct, the
unit will go back to showing the temperature.
IMPORTANT:
Certain parameters or menus may not be visible depending on the configuration of the
rest of the parameters.
English
Level 1
Level 2
Temperature regulation and control