1662H411 Ed.06
25
25
English
Technical specifications
Power supply ................................................................................................................100 - 240 V~ , 50 / 60 Hz
Maximum input power in the operation.......................................................................................10 VA at 240 V~
Maximum nominal current.............................................................................................................................15 A
Relay
- D - 20 A
NO ............................................................ (EN60730-1: 15 (15) A 250 V~ )
DEF. SP T
NC ..............................................................
( ) A 250 V~)
(EN60730-1: 15 13
Relay FAN - S - 16 A .........................................................................................(EN60730-1: 12 (9) A 250 V~)
SP T
Relay COOL - S - 16 A.......................................................................................(EN60730-1: 12 (9) A 250 V~)
SP T
Relay AUX 1 / H.CRANK. - D - 20 A NO .........................................................(EN60730-1: 15 (15) A 250 V~)
SP T
NC..........................................................
15 (13) A 250 V~)
(EN60730-1:
Relay AUX 2 - SPDT - 16 A NO..............................................................................(EN60730-1: 12 (9) A 250 V~)
NC ..............................................................................
A 250 V~)
(EN60730-1: 10 (8)
Relay AUX 3 - SPST - 16 A
NO ...................................................................(EN60730-1: 12 (9) A 250 V~)
No. of relay operations .........................................................................................EN60730-1:100.000 operations
Probe temperature range.........................................................................................................-50.0 ºC to 99.9 ºC
Resolution, setting and differential ..............................................................................................................0.1 ºC
Thermometric precision................................................................................................................................±1 ºC
Loading tolerance of the NTC probe at 25 °C............................................................................................±0.4 ºC
Input for NTC probe ...........................................................................................................................AKO-14901
Moisture probe input ..............................................................................................................Analogue, 4-20 mA
Input moisture range .........................................................................................4 mA: 0% HR - 20 mA: 100% HR
Working ambient temperature.......................................................................................................-10 ºC to 50 ºC
Storage ambient temperature
to 6
........................................................................................................-30 ºC 0 ºC
Protection degree .........................................................................................................................................IP 65
Installation category
730
....................................................................................................................II s/ EN 60
-1
Pollution degree
730
..........................................................................................................................II s/ EN 60
-1
Control device classification: Built-in assembly, with Type 1.B automatic operation action feature, for use in clean
situations, logical support (Software) class A and continuous operation. Degree of contamination 2 acc. to UNE-EN
60730-1.
Double isolation between power supply, secondary circuit and relay output.
Temperature during ball-pressure test
Accessible parts ..........................................................................75 ºC
Parts which position active elements ...........................................125 ºC
Current of radio jamming supression tests ................................................................................................270 mA
Voltage and current as per EMC tests:..................................................................................................207 V, 17 mA
Type of assembly..............................................................................................................................Fixed internal
MODBUS address..........................................................................................................................Shown on label
Dimensions...........................................................................................290 mm (W) x 141 mm (H) x 84.4 mm (D)
Internal buzzer
Summary of Contents for AKO-16624
Page 38: ...1662H411 Ed 06 38 38 ...
Page 39: ...1662H411 Ed 06 39 39 ...