Sensors to be displayed
It defines which probe will be displayed on the screen (probe 1, probe 2 or probe 3).
Display mode
It defines the information displayed on the screen during normal operation:
Ÿ
Probe and clock: It displays the probe defined in the
Sensors to be displayed
parameter, the date, time
and day of the week.
Ÿ
Probe and text: It displays the probe defined in the
Sensors to be displayed
parameter and the
description of the unit.
Ÿ
Probes, clock and text: It displays all the active probes, date, time and day of the week and the description
of the unit . The configuration of the
Sensors to be displayed
does not intervene in this mode.
Display unit
It defines the temperature display units (º Centigrade or º Fahrenheit).
Probe setting
It defines the function of the inputs of probe S1 and S3, the function of the S2 input is not configurable.
Ÿ
TEM at S1/REG at S3:
The temperature control, alarms and HACCP probe (Probe 1) is connected to the
S1 input and the temperature data logger probe (Probe 3) to the S3 input:
If probe 3 is configured as 2 defrost, the data logging deactivates.
Ÿ
TEM and REG at S3:
The temperature control, alarms and HACCP probe is also the data logger probe
(Probe 1) and it is connected in input S3, the product temperature probe is connected in the S1 input.
Decimal point
It defines is the degree's decimal points are displayed or not, and therefore the resolution of the unit.
u
Date
If configures the current date (year, month, day).
Hour
If configures the current time (day of the week, day, minute).
TEM and REG at S3
Probe 1 (Control of temperature, alarms, HACCP and data logger)
Probe 2 (Defrost / 2nd defrost)
Probe 3 (Product temperature probe / 2nd defrost)
TEM at S1/REG at S3
(According to EN 12830)
Probe 1 (Control of temperature, alarms and HACCP)
Probe 2 (Defrost / 2nd defrost)
Probe 3 (Data logger / 2nd defrost)
S 1
S 2
S 3
CON4
S 1
S 2
S 3
CON4
21