Description
Units
Min
Def
Max.
Fans stop temperature (controlled by probe 2) (Probe 2 should be active)
(ºC/ºF)
–40.0
4.0
99.9
Fans differential s2
(ºC/ºF)
0.1
1.0
20.0
Stops when compressor OFF?
No
Fans state during defrost
Connected
Disconnected
Defrost
Fans delay after defrost
(min.)
0
3
255
Stop when opening door? (It requires a digital input configured as door contact)
No
Description
Units
Min
Def
Max.
Alarm configuration:
Relative to the SP
Absolute
Rel.
Maximum alarm in sensor 1 (limits according to the alarm configuration)
(ºC/ºF)
A. Min. 50.0
320
Minimum alarm in sensor 1 (limits according to the alarm configuration)
(ºC/ºF)
–40.0 50.0 A. Max.
Alarm differential
(ºC/ºF)
0.1
1.0
20.0
Temperature alarm delay
(min.)
0
30
255
Start-up alarm delay
(min.)
0
0
255
Alarm delay after defrost
(min.)
0
0
255
On-Off door alarm delay
(min.)
0
0
255
Off-On door alarm delay
(min.)
0
0
255
Alarm relay after key (After pressing the
ESC
key, alarm silenced):
Connected
Disconnected
Con.
FAN control
ALARM control
Description
Units
Min
Def
Max.
Input 1 configuration :
Disabled
Door contact
External alarm
Severe external alarm
Remote defrost
Remote energy saving
AUX activation
Low pressure input
Thermostat control
Def.
Input 1 alarm delay
(min.)
0
0
255
Input 1 polarity:
Normally open
– The input is activated on closing the contact
Normally closed
– The input is activated on opening the contact
NC
Input 2 configuration :
Disabled
Door contact
External alarm
Severe external alarm
Remote defrost
Remote energy saving
AUX activation
Low pressure input
Thermostat control
Def.
Input 2 alarm delay
(min.)
0
0
255
DIGITAL INPUT control
23