Description
Units
Min
Def
Max.
Input 2 polarity:
Normally open
– The input is activated on closing the contact
Normally closed
– The input is activated on opening the contact
NC
Inact. with door open (time)
(min.)
0
0
255
Cold room light timing
(min.)
0
0
255
Description
Units
Min
Def
Max.
Aux. relay configuration:
Disabled
Activated by key
Activated byInput
Equal state equipment
2nd defrost
Pump down control
Equal compressor state
Pump
down
Defrost 2 duration
(min.)
0
30
255
Defrost 2 final temp.
(ºC/ºF)
–40.0
8.0
99.9
Defrost 2 sensor:
Disabled
Probe 2
Probe 3
Def.
Pump down duration
(Sec.)
1
30
1800
Pump down On delay
(Sec.)
0
60
60
Press. controller config.:
Combined HP-LP
LP indep. AC input
LP indep. digital input
HP-LP
comb.
AUXILIARY RELAY control
Description
Units
Min
Def
Max.
Access password (to parameters and set point)
00
00
99
Password to Set Point
No
Initial parameters (configures the default values and exits programming)
No
Registry interval
(min.)
0
15
60
Communication address
0
1
255
Parameters transfer:
Disabled
Send
– The unit sends the parameters to the programming key
Receive
– The unit receives the parameters from the programming key
Def.
Connected sensors:
Sensor 1
Sensor 1 and 2 Sensor 1 and 3 Sensor 1, 2 and 3
S1
Sensors to be displayed
1
1
3
Display mode:
One sensor and clock One sensor and text
Sensor, clock and text
S1 and
r.
Display unit
ºC
ºC
ºF
Decimal point
Yes
GENERAL STATUS
24