Units that include rechargeable electrical accumulators:
This unit includes accumulators that should be replaced when the unit's battery life is under the duration
assigned in its specifications. At the end of the useful life of the unit, the accumulators should be taken to a
selective waste collection centre or returned to the manufacturer.
Cautions
Using the unit not observing the manufacturer's instructions may alter the appliance's safety requirements. Only probes
supplied by AKO should be used for the it to operate correctly.
2
From –40 ºC to +20 ºC, if the NTC probe is extended to 1000 m with at least 0.5 mm cable, the maximum deviation
will be 0.25 ºC (cable for probe extension ref.
AKO-15586
).
Versions and references
Recommendations
Disconnect the voltage before carrying out any operations inside the electrical panel. All wiring should be according to
current standards and should be carried out by authorised staff. Only carry out the wiring foreseen in the wiring
diagrams. Using the electrical panel not observing the manufacturer's instructions may alter the appliance's safety
requirements. A tool is needed to remove any fixed part.
Panel installation:
It is advisable to leave a clean safety space without obstacles around the panel.
Do not knock or make sudden movements on the panel.
Carry out the wiring according to the installation manual.
The probes and their cables should
NEVER
be installed in a conduit together with power, control or feeder cables.
The earth terminals that the panels contain are installed to guarantee the continuity of earthing, however, earthing is
not carried out by the terminal and should be carried out outside the panel.
The neutral ratings are of the TT type. The IT rating should not be used.
Circuit breakers (protective switches) are of the phase/s + neutral, curve C type, guaranteeing switching and protection
against overcurrents.
Close the panel when your are not working on it.
Residual current protection outside the electrical panel according to low voltage electrotechnical regulations.
The panels meet European standard EN 61439-1.
Terminals for copper external conductors.
Checks before starting the panel up:
Power supply voltages and frequencies will be the ones that figure in the "Technical specifications" section.
Check that there are no loose parts or foreign bodies on connections or switchgear.
Check that there is no dust or damp inside the panel.
Check the correct fastening of the switchgear and components.
Condensing
unit
Condenser
fans
Evaporator
fan
Defrost
resistances
Light
Insulation
transformer
Power supply
AKO-15650
2.5 - 4 A
3 A
3 A
7,000 W
2 A
(460 W)
NO
400 V / III
50/60 Hz
AKO-15651
4 - 6.3 A
AKO-15652
6.3 - 10 A
10,200 W
AKO-15653
10 - 12 A
AKO-15680
2.5 - 4 A
7,000 W
YES
AKO-15681
4 - 6.3 A
AKO-15682
6.3 - 10 A
10,200 W
AKO-15683
10 - 12 A
14