WITH FREQUENCY CONVERTER
Operation is the same as in the previous point, but modulating the power of compressor 1 with the converter
while it remains in the neutral zone using a
PID
control.
Near the upper limit, the compressor operates at its maximum capacity, and if said limit is exceeded, more
stages/compressors are added, in accordance with the interval defined in
t02
, until returning to the neutral zone.
To avoid delays in the reaction of the installation,
t02
time is halved in the compressor equipped with an inverter.
Near the lower limit, the compressor operates at its minimum capacity, and if said limit is exceeded, it stops. The
rest of the stages/compressors will stop, in accordance with the interval programmed in
t01
, until re-entering the
neutral zone, upon which compressor 1 activates again at its minimum capacity.
6.3.- Pump Down
It is only available if the type of operation is direct (
C07
=0).
When the pressure reaches the Set Point value (
E01
) in probe 1, the last stage/compressor remaining in operation
does not stop; it continues to reduce the pressure until reaching the value configured in parameter
E08
.
In the event of a failure, if the value of
E08
is not reached, the controller will stop the compressor once the security
interval defined in
E09
has passed, displaying the message “
PdA
” (an informative message that does not affect
the unit's operation).
For this function to be active, the parameter
E08
must be configured below the Set Point (
E01
).
Upper limit
SP+E06
Pres / Temp (Probe 1)
Converter status:
NEUTRAL
ZONE
Lower limit
SP-E06
Time
SP
R1
R2
R4
R1
R2
R2
R3
R1
R2
R1
R2
R3
R3
R4
R3
100 %
100 %
0 %
OFF
(R1 OFF)
t02
t01
Example with the type of compressor rotation configured as sequential (E04=1)
12
1454H502 Ed.03