LOW AND HIGH PRESSURE ALARM DUE TO PROBES 1 AND 2
If the reading in probe 1 reaches the value set for parameter
A03
, the message
ALL
(Low
pressure) is displayed on screen, the alarm relay (if available) is activated and the compressors and
fans stop.
This alarm differential is established in parameter
A04.
If the reading in probe 1 reaches the value set for parameter
A05
, the message
ALH
(High
pressure) is displayed on screen,the alarm relay (if available) is activated and the compressors and
fans stop.
This alarm differential is established in parameter
A06
.
When the readings return to their normal values, the alarm relay deactivates but the
R
indicator remains on until
the
Q
key is pressed.
PROTECTION ALARMS
If one of the thermal protections goes off (digital inputs
I1
to
I5
, according to the configuration),
the message
At1
... is displayed on screen
At5
, the associated element (compressor or fan) stops
and the alarm relay activates (if available).
Once the protection is reset, the installation returns to its standard operation, but the alarm relay remains activated
until the
Q
key is pressed.
SEVERE EXTERNAL ALARM
When the digital input configured as a severe external alarm (
I07
or
I08=4
) is activated, the
screen displays the message
AES
, the compressors and fans stop and the alarm relay activates.
Once the cause that triggered the alarm disappears, the installation returns to its standard
operation, but the
R
indicator remains activated until the
Q
key is pressed.
PROBE 1, 2 or 3 ERROR
If an error occurs in probes 1, 2 or 3 (disconnection, cross-over or probe out of range), the
screen displays the messages
E1
,
E2
or
E3
respectively, the alarm relay activates and the
compressors and fans go on to operate according to parameters
A01
and
A02
.
Once the cause that triggered the alarm disappears, the installation returns to its standard operation, but the
R
indicator remains activated until the
Q
key is pressed.
DEPROGRAMMED CLOCK ALARM
If the unit remains without electrical supply for a period longer than 6 hours, or upon its first start-
up, the screen displays the message
Ar
, indicating that the internal clock is deprogrammed. The
unit will continue its standard operation, but if the energy save mode has been activated, it will
not start. In order to set the date and time again, adjust parameters
r01
to
r05
. Activates the alarm relay.
PUMP DOWN ALARM STOPPED DUE TO TIME
If, during pump down, the maximum interval configured in
E09
passes before the stop value
specified by
E08
is reached, the last stage will stop and the message
PdA
will be displayed. Does
not activate the alarm relay.
PRES
TEMP
PRES
TEMP
PRES
TEMP
PRES
TEMP
PRES
TEMP
PRES
TEMP
PRES
TEMP
16