9.2.- Parameters
The unit's operation parameters are organized into groups or families according to their function.
The
Def.
column shows factory-set default parameters.
The pressure values featured on the table are expressed in
bar
and those for temperature in
ºC
. If the wizard
meanwhile selects another set of units (parameter
C09
), the unit will make the conversion automatically.
IMPORTANT:
C01, C02, C04, C05, C06, C08
and
C09
are read-only parameters, editable using the
INI wizard only.
Level 1.- INSTALLATION CONFIGURATION
Level 1.- EVAPORATION CONFIGURATION
Description
Units
Min
Def
Max.
C01
Total number of compressors (with or without inverter)
-
-
-
C02
Number of stages per compressor
-
-
-
C03
Polarity of the capacity reduction contact
0
=Active when closing the contact;
1
=Active when opening the contact
0
0
1
C04
Compressor 1 with frequency inverter
0
=No;
1
=Yes
-
-
-
C05
Total number of fans (1 inverter only is considered with inverter)
-
-
-
C06
Fan control type
0
=ON/OFF;
1
=Frequency inverter
-
-
-
C07
Operation type
0
=Direct;
1
=Inverse
0
0
1
C08
Refrigerant gas type:
0=R134a 1=R404a
2=R717a 3=R22
4=R410a 5=R507a
6=R744 7=R407a 8=R407f 9=R1234y
10=R448a 11=R449a 12=R450a
13=R454A 14=R454C 15=R455A 16=R1234ze 17=R515b 18=R452A 19=R452b
-
-
-
C09
Display units (Primary-Secondary)
0
=bar-ºC
1
=psi-ºF
2
=psi-ºC
3
=bar-ºF
4
=ºC-bar
5
=ºF-psi
6
=ºC-psi
7
=ºF-bar
-
-
-
C10
Frequency inverter output type
0
=4-20 mA;
1
=0-10 V
0
0
1
InI
This indicates the configuration selected in the wizard (read only)
-
-
-
EP
Output to level 1
Description
Units
Min
Def
Max.
E01
Pressure / evaporation temperature set point
bar
E03
5
E02
E02
Evaporation set point upper limit (It cannot be set above this limit)
bar
E03
75
75
E03
Evaporation set point lower limit (It cannot be set below this limit)
bar
-0.7
-0.7
E02
E04
Compressor rotation type:
0
=Balancing, depending on the operation time
1
=Sequential (the last in is the first out)
0
0
1
E05
Compressor control type:
0
=Neutral zone;
1
=Proportional
0
0
1
E06
Evaporation regulation bandwidth
bar
0.0
2.0
50
E07
Integral time (PID inverter control)
sec.
2
5
10
E08
Stop value for pump down (If
C07
=0)
bar
-0.7
0.1
*
E09
Maximum pump down time (If
C07
=0) (0= deactivated)
sec.x10
0
0
255
EP
Output to level 1
Level 2
Level 2
*
Depending on the compressor control type: Proportional=
E01
; Neutral zone=
E01-E06
.
19
1454H502 Ed.03