40
16. Table 2 Troubleshooting
Error
Description
Corrective action
Err 1
Local communication error
•
Check the connections and wiring between the
zone control and the thermostat
Err 2
Bus communications error
•
Check the zone control’s connection to the bus.
Err 3
Damper not connected
•
Check the zone control’s connection to the
motorized system.
•
Check that the motorized system is not free.
Err 4
Damper blocked
•
Check that the zone control’s connection to the
motorized system has not shorted out.
•
Check that the motorized system is not blocked.
Err 5
No zone control sensor
•
Check that the circuit of the sensor connected to
the zone control (if any) is not open.
•
Check the configuration of the “
”
parameter.
Err 6
Zone-control sensor short-circuit
•
Check that the circuit of the sensor connected to
the zone control (if any) has not shorted out.
•
Check the configuration of the “
”
parameter.
Whenever the system detects an error, the message “Err” will be displayed in the zone where
the error has occurred. To consult the relevant error code, press “Err” when it appears.
Errors 1 and 2 have a blocking effect, and if either of them appears the thermostat cannot be
used until the error has been fixed. For the other errors, the letters “Err” will appear on the hour
digits. Pressing them displays the error code on the temperature digits.
Press the Airzone icon to clear the error and return to normal mode.
The grille and sensor errors (3, 4, 5 and 6) will only appear if these components have been set
up (the grille is set up by default and the sensor not).