25
10.2 Master Zone Control Module Initial Configuration
As said before, at initial power on, all thermostats will start in the initial set up screen,
requesting the set-up of the three initial parameters of the associated zone control module.
The first parameter to set, will indicate if the associated zone control module will have a
thermostat attached to it (master) or not (subordinate). Because the way the configuration
process is designed, it is recommended that the Master Zone control modules are to be
configured first.
This is the very first screen that the installer will see:
Where the default value will be flashing. When the Zone control module has a thermostat
attached to it, this parameter has to be changed to MASTER. To do so, touch the up arrow
once. Now,
MAs
will be flashing. To set this parameter touch on the Airzone icon once. That
action will cause the
MAs
to stay fixed and the next parameter request will appear on the
screen.
After setting the Zone control module parameter to MASTER, the screen will appear as
follows:
The second parameter, will request the installer to assign to the Zone control module its
network address
(
ZCid
).
The address range for a Master Zone control modules are 1 to 8.
Initially, address 0 will be blinking, however, No Zone control module address can be
configured as 0, therefore, the installer has to scroll to the next available address number. If
there are no other Zone control module already configured, the first number will be 1.
However, the installer can choose any number from 1 to 8, by choosing the one desired with
the arrow keys. If there is any other Zone control module already configured, its address will
not appear as available when scrolling the addresses with the arrows. For example, if there
is one Zone control module already configured with address 2, when scrolling the available
addresses, it will show 1, 3, 4, 5, 6, 7, 8, and back to 1. Like before, when the selected
address is flashing on the screen, by pushing the Airzone icon, it will set the parameter, and
the screen will go to the third parameter, which is
PERC
.
0
ZCid
su
b
ZCon