Scholar V VAIVA Maintenance & Service Manual 10/2017 Rev.2
50
5. Carefully rotate the fan motor assembly 90° and pull the assembly out of the
machine. Use care not to damage the coil or a refrigerant line when removing
the fan motor assembly.
I. Removal of the Outdoor Fan Motor Assembly (4 & 5T Units Only)
Tools Required
•
7/16” socket
• 5/16” nut driver
1. Remove the two screws that hold the condensate line to the middle front door. Note:
Do not remove or disconnect the condensate tubing.
2. Remove the eighteen screws that hold the door and carefully remove the door.
3. Disconnect the flexible duct by removing the screws at the top and bottom of the
duct.
4. The two blowers can be removed individually. Disconnect the two electrical plugs to
the blower assembly(s) that is to be removed.
5. Remove the three screws on each side of the assembly and pull the assembly out of
the unit. Use care not to damage the coil or a refrigerant line when removing the fan
motor assembly. Note: See photo on following page.