25
Scholar V VAIVA Maintenance & Service Manual 10/2017 Rev.2
Demand Control Ventilation
A field or factory installed carbon dioxide sensor controls the ventilation damper and
only opens the damper when CO
2
levels exceed a specified level. Demand control
ventilation saves energy and utility costs by ventilating the classroom based upon
occupancy.
Note:
Not available on manual fresh air damper (“B”) configuration.
Outdoor Temperature Sensor
This sensor determines the outdoor temperature at which the supplemental electric
heat turns on and is user adjustable. This may be field adjusted to the desired
temperature setting in the PLC. Please note that when the outdoor sensor activates
wet heat, the compressor does not operate.
The outdoor thermostat is located in the inlet to the condenser coil.
Outside air
temperature information
is used to switch heat pump off and electric resistance on if
outdoor air gets too cold for satisfactory heat pump heating.
OUTDOOR TEMPERATURE
SENSOR
Figure 11. Outdoor Temperature Sensor