13-2
TROUBLESHOOTING
SM FBFRPM 1-A.0 GB
ATTENTION : check for broken or loose cable lugs
fi
rst
NO SYMPTON
PROBABLE CAUSE
CORRECTIVE ACTION
9.
Only indoor fan and
compressor working.
Outdoor fan blocked.
- Remove obstructions.
10. Only indoor fan
working.
-Run capacitor of outdoor
fan motor faulty.
-Windings of outdoor fan
are shorted.
- Replace capacitor.
-Replace motor.
11. No cooling or heating
takes place, indoor
and outdoor fans
working.
- Overload safety device on
compressor is cut out (low
voltage or high
temperature)
- Compressor run capacitor
faulty.
- Compressor windings are
shorted.
- Check for proper voltage, switch off power
and try again after one hour.
- Replace compressor capacitor.
- Replace compressor.
12.
No air supply at
indoor unit,
compressor
operates.
-Indoor fan motor is blocked
or turns slowly.
-indoor fan run capacitor
faulty.
- motor windings are
shorted.
- Check voltage,repair wiring if necessary.
-Check fan wheel if it is tight enough on
motor shaft,tighten if necessary.
-Replace indoor fan motor.
13. Partial, limited air
supply at indoor unit.
Lack of refrigerant (will
accompanied by whisteling
noise) cause ice formation
on indoor unit coil in cooling
mode.
-Charge the unit after localizing leak.
14. Water
accumulates
and over
fl
ow from
indoor unit section.
Drain tube or spout of drain
pan clogged.
-Disasemble plastic drain tube from spout of
indoor unit drain pan.
15. Water dripping from
outdoor unit base.
(in heating mode)
Water drain outlet is
clogged.
-Open outdoor unit cover clean out water
outlet ,clean the base inside througly.
16.
Freeze-up of outdoor
coil in heating mode,
poor heating effect in
room, indoor fan
operates.
-Faulty outdoor thermistor.
-Faulty control cable.
- Outdoor temperature is
too low (below -10°C)
-Outdoor unit air outlet is
blocked.
-Replace thermistor.
- Repair control cable.
- Shut unit off, outdoor temp. is below design
conditions and cannot function properly.
-Remove obstructions.
Summary of Contents for YCF055
Page 45: ...8 2 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 3 Indoor Units YDF030 8 4 Outdoor Unit GCN 30NRCT...
Page 46: ...8 3 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 5 Outdoor Unit GCN 37NRC 8 6 Outdoor Unit GCN 37NRCT...
Page 47: ...8 4 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 7 Outdoor Unit YDF047 8 8 Outdoor Unit YCF055...
Page 50: ...10 2 REFRIGERATION DIAGRAMS SM FBFRPM 1 A 0 GB 10 1 2 FBF045 FBF060...
Page 92: ...14 4 EXPLODED VIEWS AND SPARE PARTS LISTS SM FBFRPM 1 A 0 GB 14 4 Indoor Unit FBF046 FBF060...
Page 109: ...15 3 OPTIONAL ACCESSORIES SM FBFRPM 1 A 0 GB 15 3 RCW RCW2 Wiring Connections as Shown on Kit...