PERFORMANCE DATA & PRESSURE CURVES
SM FBFRPM 1-A.0 GB
5.10
FBF036 / GCN 37NRCT
5.10.1
Cooling Mode at 7.5m Tubing Connection.
230V : Indoor Fan at High Speed.
ENTERING AIR
DB OD COIL (
°
C)
DATA
ENTERING AIR WB/DB ID COIL (
°
C)
15/21
17/24
19/27
21/29
23/32
15
(1)
TC
10.33 10.70 10.95 11.21 11.38
SC
6.76 7.05 7.32 7.50 7.64
PI
2.35 2.36 2.36 2.37 2.38
20
(1)
TC
9.99 10.53 10.87 11.12 11.36
SC
6.62 6.98 7.28 7.48 7.62
PI
2.56 2.56 2.57 2.59 2.59
25
TC
9.46 10.21 10.73 11.06 11.33
SC
6.45 6.85 7.22 7.43 7.57
PI
2.76 2.78 2.80 2.82 2.84
30
TC
8.84 9.63 10.40 10.77
11.09
SC
6.25 6.64 7.06 7.27 7.41
PI
2.98 3.02 3.05
3.07 3.10
35
TC
8.19 8.88
9.80
10.29 10.78
SC
5.94 6.37
6.90
7.10 7.24
PI
3.21 3.27
3.32
3.35 3.36
40
TC
7.44 8.10 8.84
9.67 10.17
SC
5.60 6.03 6.53 6.73 6.87
PI
3.47 3.52 3.58 3.62 3.66
46
TC
6.46 7.06 7.77 8.58 9.25
SC
5.16 5.53 5.95 6.16 6.30
PI
3.79 3.84 3.93 3.99 4.03
LEGEND
TC –
Total Cooling Capacity, kW
SC – Sensible Capacity, kW
PI – Power Input, kW
WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C)
ID – Indoor
OD –
Outdoor
(1) Marked area is below standard operating limits. For operating in low ambient
conditions, refer to Optional Accessories (Chapter 15).
Summary of Contents for YCF055
Page 45: ...8 2 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 3 Indoor Units YDF030 8 4 Outdoor Unit GCN 30NRCT...
Page 46: ...8 3 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 5 Outdoor Unit GCN 37NRC 8 6 Outdoor Unit GCN 37NRCT...
Page 47: ...8 4 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 7 Outdoor Unit YDF047 8 8 Outdoor Unit YCF055...
Page 50: ...10 2 REFRIGERATION DIAGRAMS SM FBFRPM 1 A 0 GB 10 1 2 FBF045 FBF060...
Page 92: ...14 4 EXPLODED VIEWS AND SPARE PARTS LISTS SM FBFRPM 1 A 0 GB 14 4 Indoor Unit FBF046 FBF060...
Page 109: ...15 3 OPTIONAL ACCESSORIES SM FBFRPM 1 A 0 GB 15 3 RCW RCW2 Wiring Connections as Shown on Kit...