11-20
CONTROL SYSTEM
SM FBFRPM 1-A.0 GB
DR
Y
(RT -
S
PT) [
o
c]
+
2
+1
0
-1
-
2
ON
OFF
ON
OFF
LOW
OFF
DR
Y
-ON
DR
Y
-OFF
ON
OFF
Time [min]
10
2
0
30
40
50
M
a
x 15 minutes
3.5
min
Note1
6
min
Note
2
COMP
& OFAN
HE1
& HE
2
IFAN
RV
M
a
x 15 minutes
5 minutes COMP
ON time
NOTES
1. When DRY is ON, the COMP is forced OFF for 3.5 min (longer
than the 3 min Min COMP- OFF time) after every 15 min of
continuous COMP operation.
2. When DRY is OFF, the COMP is forced ON for 6 min (longer
than the 3 min Min COMP- ON time) after every 15 min of
continuous COMP OFF time.
3. When DRY is changed from ON to OFF or vice versa, the
limits mentioned in (1) & (2) are ignored. The COMP operation
is only controlled by the 3 min Min OFF time and 1 min Min
ON time.
4. In DRY Mode, IFAN is LOW when COMP is ON, and is OFF
when COMP is OFF.
5. HEs are always OFF in DRY Mode.
Summary of Contents for YCF055
Page 45: ...8 2 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 3 Indoor Units YDF030 8 4 Outdoor Unit GCN 30NRCT...
Page 46: ...8 3 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 5 Outdoor Unit GCN 37NRC 8 6 Outdoor Unit GCN 37NRCT...
Page 47: ...8 4 WIRING DIAGRAMS SM FBFRPM 1 A 0 GB 8 7 Outdoor Unit YDF047 8 8 Outdoor Unit YCF055...
Page 50: ...10 2 REFRIGERATION DIAGRAMS SM FBFRPM 1 A 0 GB 10 1 2 FBF045 FBF060...
Page 92: ...14 4 EXPLODED VIEWS AND SPARE PARTS LISTS SM FBFRPM 1 A 0 GB 14 4 Indoor Unit FBF046 FBF060...
Page 109: ...15 3 OPTIONAL ACCESSORIES SM FBFRPM 1 A 0 GB 15 3 RCW RCW2 Wiring Connections as Shown on Kit...