12
AV
= WITH valve
(for wasted water)
SV
= WITHOUT valve
(for recycled water)
Qw (m
3
/h)
Air flow
Nominal
flow
HYDRAULIC CHARACTERISTICS
Model AO - Condenser supply
HYDRAULIC PRESSURE LOSS
WITH PRESSOSTAT VALVE (AV)
WITHOUT PRESSOSTAT VALVE (SV)
X 1100/X 1900
TH 3058
∆
Pw
(kPa)
100 kPa = 1 bar
HYDRAULIC CONNECTIONS
Condensate water outlets • Models AO – AR
MODELS
X 1100/X 1900
CONDENSATE WATER DRAINING HOSE
mm
Ø 20 x 25
BOTTOM TRAY OUTLET
(for hose Ø 20 x 25 mm)
Ø 7/8"
(Ø 22 mm out.)
WATER SUPPLY
WASTED WATER
RECYCLED WATER
MODELS
X 1100
X 1900
X 1100
X 1900
NOMINAL WATER FLOW
(Air to be treated 27°C 47%)
(m
3
/h)
0,70
0,95
2,1
3,05
Nominal water temperature
Inlet (°C)
Outlet (°C)
15
-
26
32
WATER PRESSURE
Minimum (kPa)
Maximum (kPa)
50
1000
-
1000
Connection on hoses
length = 1 m
Female nut
Female nut
Ø Inlet/Outlet (mm)
F 20 x 27
F 20 x 27
F 20 x 27
F 26 x 34