19
TH 3065
X 1100/X 1900
UC 33A
UC 53A
CONDENSING
UNIT
A – Discharge line
B – Liquid line
CONDENSER AT THE SAME LEVEL
AS THE INDOOR UNIT
CONDENSER
INDOOR UNIT
CONDENSER HIGHER THAN
THE INDOOR UNIT
CONDENSER
INDOOR UNIT
CONDENSER LOWER THAN THE INDOOR UNIT
INDOOR UNIT
CONDENSER
Bending of refrigeration pipes : R
≥
Ø 3,5
REFRIGERANT CHARGE in R-407C
*
per m above 2 ml
REFRIGERATION PIPEWORK
Model AR
Minimum slope downwards : 1 cm/m
Discharge Line
Liquid Line
X 1100 X 1900
Air treatment
Model
AR
g 1013
1704
Condensing units
UC 33A
UC 53A
g
g
3237
-
-
3796
Precharged linking
pipes
(maxi. length 25 m)
Discharge line
Liquid line
charge
Ø
charge
Ø
g/m*
1/2"
precharge
3/8"
55
Model
AO
(indoor unit)
1260
2850
NOTES :
For pipes between 25 and 45 m long (made on the site) the choice of the pipes (diameter) and the installation
must be made professionally.
L maxi. = 45 m
H. maxi. = 20 m
(L+H) maxi. = 45 m
h maxi. = 9 m
(L+h) maxi. = 45 m