11
Model X 1100
Model X 1900
Air flow
(m
3
/h)
Available static pressure (daPa)
Air flow
(m
3
/h)
Available static pressure (daPa)
AERAULIC CHARACTERISTICS
Models AR/AO
FRONT AND REAR AIR INTAKE WITH CLEAN AIR FILTER
TH 3057
X 1100/X 1900
Example :
Model X 1100
- Qa = 1800 m
3
/h
Standard ventilation (VS) with high rotation speed (GV)
Available static pressure : 17 daPa
Fan rotation speed : 1000 R.P.M.
Power input : 510 W
Exemple :
Model X 1900
- Qa = 2700 m
3
/h
Standard ventilation (VS) with normal rotation speed (GV)
Available static pressure : 15 daPa
Fan rotation speed : 800 R.P.M.
Power input : 480 W
VENTILATION
EQUIPMENT
"Standard ventilation"
(VS)
Motor 0,3 kW
"High ventilation"
(FV)
Motor 0,43 kW
VENTILATION
GV
High
VN
Normal
VR
Red.
FV
High
Rotational speed
motor /propeller
R.P.M.
1000
850
670
1360
Available
pressure
(daPa)
nominal
14
0
0
20
maximal
20
13
4
25
Power input (W)
510
405
260
570
ÉQUIPEMENT
DE VENTILATION
"Ventilation Standard"
(VS)
Moteur 0,43 kW
"Forte Ventilation"
(FV)
Moteur 1 kW
VENTILATION
GV
Grande
VN
Normale
VR
Réduite
FV
Forte
Vitesse de rotation
moteur/turbine (t/min) 900
800
670
1265
Pression
disponible
(daPa)
nominale
15
0
0
25
maximale
30
21
4
35
Puissance électrique
absorbée (W)
580
480
380
980
Accessory pressure loss (Qn= 2000 m
3
/h)
Hot water coil
daPa
1
Discharge plenum
daPa
2
Accessory pressure low (Qn = 3200 m
3
/h)
Hot water coil
daPa
1
Discharge plenum
daPa
2
Qa = Treated air flow
Qn = Nominal air flow