5
TECHNICAL DATA
TH 3051
X 1100/X 1900
P
ACKING
Réfrigerant
R-407C
Models
X 1100
X 1900
AR
AO
AR
AO
NOMINAL COOLING CAPACITY (1)
W
BTU
9700
33400
11700
39900
16200
55300
18000
61400
FLOW
TREATED AIR
Nominal
Mini./maxi.
m
3
/h
m
3
/h
2000
1500/2500
2000
1500/2500
3200
2500/3800
3200
2500/3800
FRESH AIR
Nominal (with accessory)
m
3
/h
180
180
285
285
AVAILABLE STATIC
PRESSURE (2)
NOMINAL/MAXI.
Standard
Ventilation
High speed
Normal speed
Reduced speed
daPa
daPa
daPa
14/20
0/13
0/4
14/20
0/13
0/4
15/30
0/21
0/4
15/30
0/21
0/4
High Ventilation (optional)
daPa
20/25
20/25
25/35
25/35
POWER
INPUT
VENTILATION
Standard
Ventilation
High speed
Normal speed
Reduced speed
W
W
W
510
450
260
510
450
260
580
500
380
580
500
380
High Ventilation (optional)
W
570
570
980
980
SOUND
PRESSURE
INDOOR UNIT (3)
High speed
Normal speed
Reduced speed
dBA
dBA
dBA
59
53
50
58
52
49
62
56
52
61
55
51
POWER SUPPLY
Nominal voltage
Voltage range
V
3 N ~ 400 V - 50 Hz
360/440
3 N ~ 400 V - 50 Hz
360/440
Total power input (1)
W
4550
3800
7260
5800
WATER CIRCUIT (1)
Wasted water
Flow
m
3
/h
0,7
0,95
Pressure drop
kPa
22
30
Recycled water
Flow
m
3
/h
2,1
3,05
Pressure drop
kPa
50
65
OUTDOOR
CONDENSING
UNIT (UC)
Model
Quantity
Air flow
Power input
Sound pressure
m
3
/h
W
dBa
7+!!)
1
3700
160
48
7+#!)
1
5000
295
53
INDOOR UNIT
Width x Depth x Height net
Width x Depth x Height packed
mm
mm
890 x 430 x1540
940 x 495 x 1690
1000 x 500 x1735
1050 x 565 x 1890
Weight net/packed
kg
136/145
151/160
182/195
199/212
DISCHARGE
PLENUM
Width x Depth x Height net
Width x Depth x Height packed
Weight net/packed
mm
mm
kg
890 x 430 x 220
1020 x 550 x 340
10/12
1000 x 500 x 260
1120 x 620 x 380
13/15
OUTDOOR
CONDENSING
UNIT (UC)
Width x Depth x Height net
Width x Depth x Height packed
Weight net/packed
mm
mm
kg
885x825x831
940x850x980
59/69
885x825x831
940x850x980
68/78
OPTIONS
Equipment "High Ventilation"
Power supply 3~230V-50 Hz (5)
ACCESSORIES
Electrical heater
Hot water coil
Front discharge plenum
Fresh air intake
Discharge duct connection flange
Intake duct connection flange
Remote control
Crankcase heater
"All seasons" system
Female pipe fittings set
Refrigerant pipes (25 m maxi)
kW
(6) kW
9
15,5
standard
9
15,5
-
-
-
-
12
29,7
standard
12
29,7
standard
-
-
-
(1) International standard ISO 51.51 conditions
Type A : 27°C/19 wet bulb. - Outside air 35°C/24°C wet bulb.
Washed water : inlet +15°C - Recycled water inlet/outlet : 29/35°C.
(2) Nominal pressure with nominal air flow
Maximum pressure with minimum air flow
(3) Total sound pressure in dBA (4m) under nominal conditions in a room of 1000 m
3
(reverberation 0.83 sec)
(4) Total sound pressure in dBA (4m) under nominal conditions in open space on reflecting surface.
(5) Voltage range minimum 198V maximum 242 V (the other electrical values are not changed)
(6) Hot water coil 90/80°C - Treated air 20°C - 50% with nominal air flow.
with nominal voltage without accessory