27
3-19. Suspending the Indoor Unit
Depending on the ceiling type:
•
Insert suspension bolts (Fig. 3-58)
or
•
Use existing ceiling supports or construct a suitable
support (Fig. 3-59).
Insert
Hole-in-anchor
Hole-in-plug
Concrete
Suspension bolt (M10 or 3/8")
(field supply)
Fig. 3-58
Ceiling support
Ceiling tiles
Fig. 3-59
WARNING
It is important that you use extreme care in supporting
the indoor unit inside the ceiling. Ensure that the ceiling
is strong enough to support the weight of the unit. Before
hanging the unit, test the strength of each attached
suspension bolt.
(1) When placing the unit inside the ceiling, determine the
pitch of the suspension bolts referring to the dimensional
data as shown in Fig. 3-56 and Table 3-4.
Tubing must be laid and connected inside the ceiling when
suspending the unit. If the ceiling is already constructed,
lay the tubing into position for connection to the unit before
placing the unit inside the ceiling.
(2) Screw in the suspension bolts allowing them to protrude
from the ceiling (Fig. 3-58). (Cut the ceiling material, if
necessary.)
(3) Thread the 3 hexagonal nuts and 2 washers (field supply)
onto each of the 4 suspension bolts (Figs. 3-60 and 3-61).
Use 1 nut and 1 washer for the upper part, and 2 nuts and
1 washer for the lower part, so that the unit will not fall off
the suspension lugs.
Nuts and washers
(use for upper and lower)
Suspension lug
Double nuts
Suspension bolt
Notch
Fig. 3-60
Suspension bolt
Double nuts
Hexagonal nut
Fig. 3-61
●
This shows an example of installation.
Air outlet duct
Air-outlet grille
Ceiling material
Indoor unit
Air-intake
grille
Suspension
bolt
Bolt anchor
Air-intake
duct
Fig. 3-62
Airwell̲PAC-i̲eng.indb 27
Airwell̲PAC-i̲eng.indb 27
2009/07/09 16:13:26
2009/07/09 16:13:26
Summary of Contents for OU-PSINV-25HR