12a-38
CONTROL SYSTEM
Revision
0
12A.20. System diagnostics
Pressing Mode button for 5-10 seconds in SB or any other operation mode will activate
diagnostic mode by the acknowledgment of 3 short beeps and lighting of COOL and HEAT LEDs.
In diagnostic mode, system problems will be indicated by blinking of Heat & Cool LEDs.
The coding method will be as follow:
Heat led will blink 5 times in 5 seconds, and then will be shut off for the next 5 seconds. Cool led
will blink during the same 5 seconds according to the following table:
No
Problem
1
2
3
4
5
1
RT1 is disconnected
○
●
●
●
●
2
RT1 is shorted
○
●
●
●
○
3
RV Fault
○
●
●
○
●
4
RT2 is disconnected
●
○
●
●
●
5
RT2 is shorted
●
○
●
●
○
6
(Reserved)
●
○
●
○
●
7
RT2 temp reading doesn’t change
●
○
●
○
○
8
RT3 is disconnected
●
●
○
●
●
9
RT3 is shorted
●
●
○
●
○
10
(Reserved)
●
●
○
○
●
11
RT3 temp reading doesn’t change
●
●
○
○
○
12
RT2 & RT3 temp reading doesn’t change
●
○
○
○
○
13
PG motor no feedback error
●
●
●
●
●
○ - ON,
● - OFF
Notes:
1. If faults occur in more than one thermistor (except case number 12 on the table
above), only one fault will be indicated according to the following order: RT3, RT2, RT1.
2. A/C will jump out to normal mode if sending a command by the R/C in the system
diagnostics mode. If this command from the R/C contains a Group ID, this ID will become
the new Group ID of the ELCON unit.
Summary of Contents for ONG 12
Page 4: ......
Page 19: ...4 1 OUTLINE DIMENSIONS Revision 0 4 OUTLINE DIMENSIONS 4 1 FLO N 7 9 12 14 4 2 FLO N 18 24...
Page 20: ...4 2 OUTLINE DIMENSIONS Revision 0 4 3 FLO N 30 4 4 ONG 7 9 12 14 RC 150m m...
Page 22: ...4 4 OUTLINE DIMENSIONS Revision 0 4 7 OU7 24 RC 4 8 GC 30 N RC...
Page 23: ...4 5 OUTLINE DIMENSIONS Revision 0 4 9 OU8 30 RC...
Page 60: ...8 2 WIRING DIAGRAMS Revision 0 8 2 Indoor Unit FLO 18 24 N LCD...
Page 61: ...8 3 WIRING DIAGRAMS Revision 0 8 3 Indoor Unit FLO 30 N...
Page 63: ...8 5 WIRING DIAGRAMS Revision 0 8 6 Outdoor Unit ONG7 1PH R410A...
Page 64: ...8 6 WIRING DIAGRAMS Revision 0 8 7 Outdoor Unit OU7 24 OU8 30 1PH R410A...
Page 66: ...8 8 WIRING DIAGRAMS Revision 0 8 10 Outdoor Unit OU8 33 3PH R410A...
Page 68: ...9 2 ELECTRICAL CONNECTIONS Revision 0 9 3 FLO 30 N 3PH...
Page 70: ...10 2 REFRIGERATION DIAGRAMS Revision 0 10 1 2 FLO 9 12 14 N R410A...
Page 72: ...10 4 REFRIGERATION DIAGRAMS Revision 0 10 1 4 FLO 24 N R410A...
Page 135: ...14 3 OPTIONAL ACCESSORIES Revision 0 14 3 RCW RCW2 Wiring Connections as Shown on Kit...
Page 137: ...15 5 OPTIONAL ACCESSORIES Revision 0...
Page 138: ...15 6 OPTIONAL ACCESSORIES Revision 0...
Page 139: ...15 7 OPTIONAL ACCESSORIES Revision 0...
Page 140: ...15 8 OPTIONAL ACCESSORIES Revision 0...
Page 141: ......