12b-16
CONTROL SYSTEM
Revision
0
12B.4.15 Protection
•
When all relays meet their function requirements at the same time, there should be an
interval of 0.5 second between every two relays. The action procedures are as follows:
ON state:
AHEAT
RV
OFAN —> COMP
OFF state:
AHEAT
RV
OFAN
COMP
12B.4.16
Compressor delay protection
•
At startup if the operation mode is not change, compressor will keep on running during the
first 5 minutes, and it will delay for 3 minutes for a re-start once it was turned off.
•
Compressor starts at 3 minutes delay unless:
•
Power is on for the first time or power off lasts for 3 minutes, COMP has no 3 minutes
delay protection;
12B.4.17 RV control
•
In cooling or drying mode or fan mode, RV is off.
•
In heating mode, RV will turns on.
•
Switching between heating mode to other modes, or shutting off in heating mode, RV
delays 2 minutes before turning off.
12B.4.18 Diagnostic
•
If MCU detect that one of the sensors RT, ICT or, OCT is blow -40ºC or over 85ºC,
the sensor is invalid and will be indicated (see 3.13).But the air-conditioner operates
continuously.
•
In Cooling or Heating mode, COMP turns on for 20 minutes and turns off for 5 minutes, it is
continuously cycle by cycle. In Dry mode, COMP turns on for 10 minutes and turns off for 6
minutes.
•
If RT is invalid, system runs at cycle by cycle mode.
•
If OCT and ICT are invalid, system runs at cycle by cycle mode too.
•
For cooling only unit’s type, if ICT is wrong, system runs at cycle by cycle mode.
Summary of Contents for ONG 12
Page 4: ......
Page 19: ...4 1 OUTLINE DIMENSIONS Revision 0 4 OUTLINE DIMENSIONS 4 1 FLO N 7 9 12 14 4 2 FLO N 18 24...
Page 20: ...4 2 OUTLINE DIMENSIONS Revision 0 4 3 FLO N 30 4 4 ONG 7 9 12 14 RC 150m m...
Page 22: ...4 4 OUTLINE DIMENSIONS Revision 0 4 7 OU7 24 RC 4 8 GC 30 N RC...
Page 23: ...4 5 OUTLINE DIMENSIONS Revision 0 4 9 OU8 30 RC...
Page 60: ...8 2 WIRING DIAGRAMS Revision 0 8 2 Indoor Unit FLO 18 24 N LCD...
Page 61: ...8 3 WIRING DIAGRAMS Revision 0 8 3 Indoor Unit FLO 30 N...
Page 63: ...8 5 WIRING DIAGRAMS Revision 0 8 6 Outdoor Unit ONG7 1PH R410A...
Page 64: ...8 6 WIRING DIAGRAMS Revision 0 8 7 Outdoor Unit OU7 24 OU8 30 1PH R410A...
Page 66: ...8 8 WIRING DIAGRAMS Revision 0 8 10 Outdoor Unit OU8 33 3PH R410A...
Page 68: ...9 2 ELECTRICAL CONNECTIONS Revision 0 9 3 FLO 30 N 3PH...
Page 70: ...10 2 REFRIGERATION DIAGRAMS Revision 0 10 1 2 FLO 9 12 14 N R410A...
Page 72: ...10 4 REFRIGERATION DIAGRAMS Revision 0 10 1 4 FLO 24 N R410A...
Page 135: ...14 3 OPTIONAL ACCESSORIES Revision 0 14 3 RCW RCW2 Wiring Connections as Shown on Kit...
Page 137: ...15 5 OPTIONAL ACCESSORIES Revision 0...
Page 138: ...15 6 OPTIONAL ACCESSORIES Revision 0...
Page 139: ...15 7 OPTIONAL ACCESSORIES Revision 0...
Page 140: ...15 8 OPTIONAL ACCESSORIES Revision 0...
Page 141: ......