12b-10
CONTROL SYSTEM
Revision
0
12B.3.12
High Pressure Protection
•
If ICT >= 61ºC, OFAN turn off. If ICT <= 55ºC, OFAN turn on.
•
If (ICT >= 66ºC) for duration of 10 seconds, COMP turn off. If ICT <= 52ºC, COMP turn on.
Note:
If ICT is invalid, High Pressure protection cannot be activated.
12B.3.13 Auxiliary Electric Heating
AHEAT will turn on, if all the following conditions are met:
•
COMP is on for 60 seconds;
•
RT <= 20ºC;
•
IFAN run at least at LOW speed;
•
RT <= SPT – 2ºC;
•
ICT <= 50ºC.
AHEAT will turn off, if one of the following conditions is filled:
•
RT > 21ºC;
•
COMP or IFAN stop;
•
RT >= SPT - 1ºC;
•
ICT >= 55ºC.
Note:
1. If ICT or RT is invalids, AHEAT will not be activated.
2. When the system turns off, if the AHEAT does not operate before, IFAN operates
according to the hot keep condition, otherwise, IFAN should turn off after 30 seconds’ at
supper low fan speed (Note: F/S type in low speed) to blow off the remaining heat.
ICT (ºC)
66
61
55
52
>= 10s >= 3 Min
COMP Any
Off
OFAN Any
Off
Summary of Contents for ONG 12
Page 4: ......
Page 19: ...4 1 OUTLINE DIMENSIONS Revision 0 4 OUTLINE DIMENSIONS 4 1 FLO N 7 9 12 14 4 2 FLO N 18 24...
Page 20: ...4 2 OUTLINE DIMENSIONS Revision 0 4 3 FLO N 30 4 4 ONG 7 9 12 14 RC 150m m...
Page 22: ...4 4 OUTLINE DIMENSIONS Revision 0 4 7 OU7 24 RC 4 8 GC 30 N RC...
Page 23: ...4 5 OUTLINE DIMENSIONS Revision 0 4 9 OU8 30 RC...
Page 60: ...8 2 WIRING DIAGRAMS Revision 0 8 2 Indoor Unit FLO 18 24 N LCD...
Page 61: ...8 3 WIRING DIAGRAMS Revision 0 8 3 Indoor Unit FLO 30 N...
Page 63: ...8 5 WIRING DIAGRAMS Revision 0 8 6 Outdoor Unit ONG7 1PH R410A...
Page 64: ...8 6 WIRING DIAGRAMS Revision 0 8 7 Outdoor Unit OU7 24 OU8 30 1PH R410A...
Page 66: ...8 8 WIRING DIAGRAMS Revision 0 8 10 Outdoor Unit OU8 33 3PH R410A...
Page 68: ...9 2 ELECTRICAL CONNECTIONS Revision 0 9 3 FLO 30 N 3PH...
Page 70: ...10 2 REFRIGERATION DIAGRAMS Revision 0 10 1 2 FLO 9 12 14 N R410A...
Page 72: ...10 4 REFRIGERATION DIAGRAMS Revision 0 10 1 4 FLO 24 N R410A...
Page 135: ...14 3 OPTIONAL ACCESSORIES Revision 0 14 3 RCW RCW2 Wiring Connections as Shown on Kit...
Page 137: ...15 5 OPTIONAL ACCESSORIES Revision 0...
Page 138: ...15 6 OPTIONAL ACCESSORIES Revision 0...
Page 139: ...15 7 OPTIONAL ACCESSORIES Revision 0...
Page 140: ...15 8 OPTIONAL ACCESSORIES Revision 0...
Page 141: ......