Electrical Control Function
80
Electrical Control System
1. Electrical Control Function
1.1 Definition
T1: Room Air Thermistor (RAT)
T2: Indoor Coil Thermistor (ICT)
T2B: Indoor Return Gas Thermistor (RGT)
T3: Outdoor Coil Thermistor (OCT)
T4: Outdoor Air Thermistor (OAT)
T5: Compressor Discharge Thermistor (CTT)
1.2 Main Protection
1.2.1 Three minutes delay at restart for compressor.
1.2.2 Temperature protection of compressor discharge
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules:
----If 102
℃
<T5<115
℃
, decrease the frequency to the lower level every 2 minutes till to F1.
---If T5>115
℃
for 10 seconds, the compressor will stop and restart till T5<90
℃
.
1.2.3 Sensor protection at open circuit and breaking disconnection.
1.2.4 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later.
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function.
1.2.5 Fan speed is out of control(Excluding JOSI-DKH009-N11)
When indoor fan speed keeps too low for certain time, the unit will stop and the LED will display the failure.
1.2.6 Zero crossing detection error protection(only for JOSI-DKH009-N11)
If AC detects time interval is not correct for continuous 240s, the unit will stop and the LED will display the
failure. The correct zero crossing signal time interval should be between 6-13ms.
1.2.7 Inverter module protection
The Inverter module has a protection function about current, voltage and temperature. If these protections
happen, the corresponding code will display on indoor unit and the unit will stop working.
1.2.8 Compressor current limit protection
If the compressor current exceeds the current limit value for 10 seconds, the compressor frequency will be
limited as below table.
Cooling mode:
Current frequency
(
Hz
)
Current limit value
(
A
)
Frequency limit
COOL_F16
ICOOLLMT12
Decrease the frequency to COOL_F4 and run at COOL_F4 for
3 minutes.
After that, the frequency will be adjusted according to the
capacity demand and rise to the upper level every 3 minutes
(When the frequency>COOL_F4 via capacity demand).
COOL_F15
ICOOLLMT11
COOL_F14
ICOOLLMT10
COOL_F13
ICOOLLMT9
COOL_F12
ICOOLLMT8
COOL_F11
ICOOLLMT7
COOL_F10
ICOOLLMT6
COOL_F9
ICOOLLMT5
COOL_F8
ICOOLLMT4
COOL_F7
ICOOLLMT3
Summary of Contents for johnson JOAU-ZCY218-H11
Page 13: ...Indoor Units Indoor Units 11 Part 2 Indoor Units DKH Type 12 Light Commercial 22 ...
Page 36: ...Dimensions 34 Indoor Units ...
Page 38: ...Service Space unit mm 36 Indoor Units 3 3 Console ...
Page 40: ...Wiring Diagrams 38 Indoor Units JOSI DCD012 N11 JOSI DAQ012 N11 ...
Page 51: ...Dimensions 50 Outdoor Units JOAU ZCY536 H11 ...
Page 55: ...Wiring Diagrams 54 Outdoor Units 4 Wiring Diagrams JOAU ZCY218 H11 JOAU ZCY327 H11 ...
Page 56: ...Wiring Diagrams Outdoor Units 55 JOAU ZCY430 H11 JOAU ZCY536 H11 ...