Troubleshooting
112
Electrical Control System
2.4.2.5 High pressure protection (ODU P1) (For JOAU-ZCY430-H11, JOAU-ZCY536-H11)
High pressure protection
Judge 1: Whether the wiring
between the high pressure
switch and main control
board is connected well or
correctly
Method: Short connect the
high pressure protector
socket, check whether the
system can run normally
Yes
No
Connect it well
Replace outdoor main board
No
Replace high pressure protector
Yes
Judge 2: Whether
the high pressure
protector is broken
Check whether
the refrigerant
system is ok
Judge 3: Check whether the
outdoor ambient
temperature is higher than
50
℃
No
Stop the unit
Yes
Judge 4: Check whether the
outdoor unit is bad
ventilation
No
Make the outdoor unit ventilate well
Yes
Judge 5: Check whether the
heat exchanger is dirty
Clean the heat exchanger
Yes
Judge 6: Check whether the
refrigerant pipe is blocked
Let the refrigerant out, then use the
high pressure nitrogen or refrigerant to
blow pipe, vacuumize and charge the
refrigerant again
Yes
Summary of Contents for johnson JOAU-ZCY218-H11
Page 13: ...Indoor Units Indoor Units 11 Part 2 Indoor Units DKH Type 12 Light Commercial 22 ...
Page 36: ...Dimensions 34 Indoor Units ...
Page 38: ...Service Space unit mm 36 Indoor Units 3 3 Console ...
Page 40: ...Wiring Diagrams 38 Indoor Units JOSI DCD012 N11 JOSI DAQ012 N11 ...
Page 51: ...Dimensions 50 Outdoor Units JOAU ZCY536 H11 ...
Page 55: ...Wiring Diagrams 54 Outdoor Units 4 Wiring Diagrams JOAU ZCY218 H11 JOAU ZCY327 H11 ...
Page 56: ...Wiring Diagrams Outdoor Units 55 JOAU ZCY430 H11 JOAU ZCY536 H11 ...