10 - TECHNICAL INFORMATION
10.2 GENERAL TECHNICAL DATA
10.3 ELECTRICAL DATA
COOLING AE 30°C
Cooling capacity
1 kW
1,57
2,10
4,03
Compressor power input
1 kW
0,498
0,640
1,29
Total power input
1 kW
0,542
0,700
1,48
EER
1
2,90
3,00
2,72
HEATING AE –5°C
Heat output
4 kW
1,86
2,35
5,10
Compressor power input
4 kW
0,320
0,379
0,846
Total power input
4 kW
0,360
0,431
0,996
COP
4
5,17
5,45
5,12
COMPRESOR
Type of compressors
ROT
ROT
ROT
No. of Compressors
Nr
1
1
1
Type of refrigerant
R410A
R410A
R410A
Refrigerant charge
Kg
0,80
0,75
1,45
FANS
Type of fans
CFG
CFG
CFG
Number of fans
Nr
2
2
2
Air flow
mc/h
200
300
650
Absorbed capacity by fans
5 kW
0,040
0,052
0,150
Available head nominal
Pa
40
40
40
Max outside static pressure
Pa
120
120
120
CONNECTIONS
Condensate discharge
26
26
26
POWER SUPPLY
Standard power supply
V
230/1/50
230/1/50
230/1/50
NOISE LEVELS
Sound pressure level (1m)
6 dB(A)
39
41
46
HEATING AE 7°C
Heat output
3 kW
1,81
2,33
5,00
Compressor power input
3 kW
0,401
0,541
1,12
Total power input
3 kW
0,441
0,593
1,27
COP
3
4,10
3,93
3,94
COOLING AE 35°C
Cooling capacity
2 kW
1,63
2,17
4,23
Compressor power input
2 kW
0,523
0,674
1,33
Total power input
2 kW
0,567
0,734
1,519
EER
2
2,87
2,96
2,78
SIZES
200
300
650
(1)
AE 30°C
: data referred to the following conditions:
Outdoor air temperature: 30°C BS/ 22.0°C BU
Internal air temperature: 27°C BS/ 19°C BU
nominal air flow
(2)
AE 35°C
: data referred to the following conditions:
Outdoor air temperature: 35°C BS/ 24.0°C BU
Internal air temperature: 27°C BS/ 19°C BU
nominal air flow
(3)
AE 7 °C
:data referred to the following conditions:
Outdoor air temperature: 7°C BS/ 6°C BU
Internal air temperature: 20°C BS/ 15°C BU
nominal air flow
(4)
AE –5°C
:data referred to the following conditions:
Outdoor air temperature: -5°C BS/ -5.4°C BU
Internal air temperature: 20°C BS/ 15°C BU
nominal air flow
(5) the fan absorptions refer to the air flows of the heating operation (conditions as
indicated in note (2)) and 40Pa available head
(6) I livelli sonori si riferiscono ad unità a pieno carico nelle condizioni nominali di prova.
The sound pressure is measured at 1 m from the external surface of the unit in open
field conditions.
Power supply 230/1/50Hz +/- 10%
F.L.A. FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS
F.L.A. - Compressor 1
A
2,2
3,1
6,8
F.L.A. - Single supply fan
A
1,2
1,2
1,2
F.L.A. - Single exhaust air fan
A
1,2
1,2
1,2
F.L.A. - Total
A
5,6
6,5
10,2
L.R.A. LOCKED ROTOR AMPERES
L.R.A. - Compressor 1
A
12
16,5
37
F.L.I. FULL LOAD POWER INPUT (AT MAX ADMISSIBLE CONDITION)
F.L.I. - Compressor 1
kW
0,47
0,69
1,52
F.L.I. - Single External Fan
kW
0,165
0,165
0,165
F.L.I. – Single exhaust air fan
kW
0,165
0,165
0,165
F.L.I. - Total
kW
1,03
1,25
2,08
M.I.C. MAXIMUM INRUSH CURRENT
M.I.C. - Value
A
14,4
18,9
39,4
Size
200
300
650