8 - CONTROL
90 Minfiltri
Filter min. control signal value
%
20
1
92 SetAlarmFreeze
SetPoint for water coil antifreeze alarm
°C
4
1
93 DeltaAlarmFreeze
Differential for the water coil antifreeze alarm reset
°C
2
1
94 Tstarting
Min. interval between start/stop of two compressors
sec
10
1
96 FanPFcorr
PWM fan power factor correction
1=500ns
3800
1
97 SetURCool
UR SetPoint in cooling
%
60
0
99 TimeByPassFiltri
Clogged filter alarm Bypass time
sec
30
1
100 SetAlarmOverheating
Setpoint for water coil overtemperature
°C
90
1
101 DeltaAlarmOverheating
Differential for water coil overtemperature alarm reset
°C
2
1
102 DeltaMinH2OHeat
Difference of water coil air temperature during heating with water at TH2OminHeat
°C
10
1
103 DeltaMaxH2OHeat
Difference of water coil air temperature during heating with water at TH2OMaxHeat
°C
32
1
105 TH2OMinHeat
Coil hot water temperature that provides the DeltaMinH2OHeat
°C
38
1
106 TH2OMaxHeat
Coil hot water temperature that provides the DeltaMaxH2OHeat
°C
70
1
107 DeltaMinH2OCool
Difference of water coil air temperature during cooling with water at TH2OMinCool
°C
10
1
108 DeltaMaxH2OCool
Difference of water coil air temperature during cooling with water at TH2OMaxCool
°C
32
1
109 TH2OMinCool
Coil hot water temperature that provides the DeltaMinH2OCool
°C
5
1
110 TH2OMaxCool
Coil hot water temperature that provides the DeltaMaxH2OCool
°C
12
1
111 TimeOpenValve
Water coil opening time
sec
140
1
112 TimeCorrection
Water coil opening correction time
sec
40
1
119 LimTambHeat
Compressor operating limit in heating for ambient temperature
°C
16
1
120 LimTambCool
Compressor operating limit in cooling for ambient temperature
°C
30
1
126 MaxVarDeltaBatt
Max DeltaBatteria variation beyond which is performed the water valve modulation reset
0: it excludes the reset on the DeltaBatteria variation
°C
4
1
127 MaxVarSetOut
Max SetMandata variation beyond which is performed the water valve modulation reset 0:
it excludes the reset on the SetMandata variation
°C
2
1
128 MinApValvH2O
Min. opening of the handling water coil valve (phisical threshold to have the flow)
2
1
129 RiduzDeltaBattH2O
Reduction coefficient to the coil delta in the valve modulation of initial opening
%
70
1
131 OffSetTin
Inlet probe offset
°C
0
1
132 OffSetTout
Outlet probe offset
°C
0
1
133 OffSetText
External temperature probe offset
°C
0
1
135 OffSetTfreeze
Antifreeze probe offset
°C
0
1
137 OffSetTH2O
system water probe offset
°C
0
1
139 OffSetURProbe
Ambient humidity probe offset
%
0
1
141 OffSetURProbeThrow
Outlet humidity probe offset
%
0
1
149 MinProbePress
Pressure value corresponding to 4mA of the return pressure transducer /exhaust air coil
bar
0
1
150 MaxProbePress
Full scale value of the return pressure transducer/exhaust air coil
bar
50
1
151 OffsetProbePress
return pressure transducer offset/exhaust coil
bar
0
1
165 MODBusAddress
ModBus serial address
55
1
166 Baud Rate
Baud Rate (0=4800 / 1=9600)
0
1
167 Parity
Parity (0=no / 1=si)
0
1
168 CANaddressNode
CANOPEN board address
1
1
180 TimeOnURfreeze
Humidifier activation time in antifreeze
min
5
1
181 TimeOffURfreeze
Humidifier off wait time in antifreeze
min
60
1
182 PotURfreeze
Modulating output level of the humidifier in antifreeze
%
20
1
183 hAmbStopComp
Ambient enthalpy setpoint that leads to compressor stop
g/kg
7,2
1
184 DeltahAmb
Ambient enthalpy delta for compressor enabling
g/kg
0,7
1
185 MaxRip_0
Max. value of the return fan control (with SetUpFanRip= 0)
%
100
1
186 MinRip_0
Min. value of the return fan control (with SetUpFanRip= 0)
%
20
1
187 MaxMan_0
Max. value of the supply fan control (with SetUpFanMan= 0)
%
100
1
188 MinMan_0
Min. value of the supply fan control (with SetUpFanMan= 0)
%
20
1
189 NomHeatRip_0
Nominal value of the return fan control in Heat (with SetUpFanRip= 0)
%
50
1
190 NomCoolRip_0
Nominal value of the return fan control in Cool (with SetUpFanRip= 0)
%
50
1
191 NomHeatMan_0
Nominal value of the supply fan control in Heat (with SetUpFanMan= 0)
%
50
1
192 NomCoolMan_0
Nominal value of the supply fan control in Cool (with SetUpFanMan= 0)
%
50
1
198 MinTThrowHeat
Min. supply temperature in Heat
°C
10
1
199 DeltaTThrowHeat
Differential for the MinTThrowHeat calculation
°C
2
1
200 MaxTThrowHeat
Keypad address
°C
45
1