![Airwell Airflow 2020 Installation And Operating Manual Download Page 21](http://html.mh-extra.com/html/airwell/airflow-2020/airflow-2020_installation-and-operating-manual_2879847021.webp)
21
6 - ELECTRIC CONNECTIONS
In case of alarm signalling from a fire surveying station,
the unit can put the ambient:
-
in negative pressure
-
in pressure
-
maintains a neutral ambient
Set parameter 91 :
= 0neutral ambient
= 1 depressurized ambient
= 2 ambient in pressure
Remove the jumper
11cn1 and 3cn1
on the
X1
terminal block.
Connect the alarm signalling to terminals
11cn1 and
3cn1
.
Humidifier signalling (alarm UR%)
Signalling of the winter humidification function block
RCW19 AMBIENT THERMOSTAT
Connect the RCW19 ambient thermostat as indicated
in the figure
.
Connections :
•
3x0,34mm
2
shielded
•
max. length 80 m
X1
RCW15 - REMOTE CONTROL WITH TOUCH SCREEN DI-
SPLAY
Remote user keypad, to control the unit main functions.
To use the keyboard, you need:
•
12Vdc power supply unit (supplied separately)
•
serial communication module (supplied separately)
For details, see instructions accessory.
RCW15 opt.
Pressing any button of the thermostat there is not
control / communication check the fuses (FU 12v and
FU NET).
If the fuses are burnt replace them and check the
connections.