START-UP SEQUENCE
7 - START-UP
START-UP SEQUENCE
√
HEATER OPERATION CHECK (option)
1
set the unit to heating mode
2
temporarily set parameter 208=1
3
with the unit not powered, open the compressor's fuse holder (FU1 to sizes 200-650 / FUG to sizes 70-120)
4
start the unit and wait until the heaters begin treating the supply air
5
with the unit not powered, set parameter 208=0
6
close the compressor's fuse holder
√
HUMIDIFIER OPERATION CHECK (option, sizes 200-650 only)
1
set the unit to heating mode
2
through the ambient thermostat (parameter P05) or service keypad (parameter 30),
set the humidity set-point to 90%
3
check that the cylinder fills with water and starts boiling
4
a full cylinder combined with a very low current absorption value (with respect to the nominal value indicated
on the cylinder) and a delay in boiling do not imply any malfunctions, but indicate that the water is poorly
conductive and that the cylinder will take some time to reach full power