8 - CONTROL
ALARMS
Alarm
Description
Possible cause
E00
No communication between thermostat and unit Check wiring between the thermostat and the unit board
Loose wiring, possible failure of the board or the thermostat following an
anomaly related to the power supply voltage
M
E01
Inlet temp. Probe fault
Check wiring.
Potential probe failure, replace it
A
E02
Outlet temp. Probe fault
Check wiring.
Potential probe failure, replace it
A
E03
Externe air temperature probe fault
Check wiring.
Potential probe failure, replace it
A
E05
Ambient humidity probe fault
Replace the thermostat.
A
E07
Supply humidity probe fault
Check wiring.
Potential probe failure, use a series tester to make sure that the generated
signal is within the range (4-20 mA).
Replace the probe
A
E10
Water temperature probe fault
Check wiring.
Potential probe failure, replace it.
A
E11
Fire alarm
If there is a fire sensor: check the sensor and the wiring.
If there is no fire sensor: check the input jumper.
M
E12
Electric heater alarm
If heaters are present: check if powered
If heaters are not present: check jumper on input (11cn1 - 7cn1)
Dirty air filter
Dirty heaters (no filter)
No airflow (control the fan)
Heater reset
M
E13
Compressor low pressure
SUMMER
insufficient supply air flow rate in ambient
-
filters air dirty
-
obstacles air distribution system
-
supply fan fault
Cooling circuit anomaly - Contact a qualified technician.
WINTER
insufficient exhaust air flow rate
-
filters air dirty
-
return installation obstacles from ambient
-
exhaust fan fault
-
problems during defrost
A / M
E14
Compressor high pressure
WINTER
insufficient supply air flow rate in ambient
-
filters air dirty
-
obstacles air distribution system
-
supply fan fault
SUMMER
insufficient exhaust air flow rate
-
filters air dirty
-
return installation obstacles from ambient
-
exhaust fan fault
M
E18
Humidifier alarm
problems related to the humidifier
M
E19
Outlet high temp. signaling
the temperature of the air supplied in the room is too high;
-
the air is not compatible with the unit's operating limits
-
insufficient supply air flow rate in ambient
-
filters air dirty
-
obstacles air distribution system
-
supply fan fault
A
E20
Outlet 2 high temp. signaling
the temperature of the air supplied in the room is too high;
-
the air is not compatible with the unit's operating limits
-
insufficient supply air flow rate in ambient
-
filters air dirty
-
obstacles air distribution system
-
supply fan fault
A / M