47
ARTUS™ Technical Manual 9690348 v3_04_2020
Te
ch
nic
al
Technical Data
Mechanical and Electrical Data
Notes Units
AR
C66-41PE1H-7
ARX66-41PE1H-7
AR
C66-42PE1H-7
ARX66-42PE1H-7
AR
C66-21PE1H-7
ARX66-21PE1H-7
AR
C66-41PE1L-7
ARX66-41PE1L-7
AR
C66-42PE1L-7
ARX66-42PE1L-7
AR
C66-21PE1L-7
ARX66-21PE1L-7
Capacity
Nom Cooling (Gross)
(1)
kW
2.86
2.67
2.86
2.84
2.66
2.84
Nom Heating (Gross)
(2)
kW
1.43
0.23
N/A
1.57
0.23
N/A
Nom Heating (Gross)
(3)
kW
7.05
1.19
N/A
7.23
1.19
N/A
Fan Power Input (Fan Gain)
(4)
W
12.7
14.8
12.7
12.7
14.8
12.7
Weight
Machine
(5)
kg
21.5
22.0
20.6
21.5
22.0
20.6
Operating
(5)
kg
22.3
23.5
21.4
22.3
23.5
21.4
Waterside
Water volume
l
0.9
0.9 / 0.3
0.9
0.9
0.9 / 0.3
0.9
Water flow rate - Cooling (1)
l/s
0.23
0.21
0.23
0.11
0.11
0.11
Unit pressure drop - Cooling (1)
(6)
kPa
152
98
116
96
75
87
Water flow rate - Heating (2)
l/s
0.07
0.01
N/A
0.08
0.01
N/A
Unit pressure drop - Heating (2)
(6)
kPa
14
18
N/A
47
18
N/A
Water flow rate - Heating (3)
l/s
0.15
0.03
N/A
0.16
0.03
N/A
Unit pressure drop - Heating (3)
(6)
kPa
72
21
N/A
179
21
N/A
Fan & Motor
Motor Type
EC
Quantity x Motor Size
W
1 x 85
Speed @0Pa ESP / Maximum ESP
rpm
741 / 1487
Maximum ESP
Pa
98
Overall Sound Power (supply and return)
dBA
52
54
52
52
54
52
Connections
Water Inlet
inches
1/2” BSPP
Water Outlet
inches
1/2” BSPP
Electrical Data
Nominal Run Amps
(7)
A
0.201
0.192
0.152
0.201
0.192
0.152
Evaporator Fan - Per Fan
Motor Rating
W
85
Nominal Motor Running Load
(8)
A
0.09
Full Load Amps
A
0.7
(1) Entering air 27°C / 46% RH - supply water 6°C (high flow coil water Δt = 3K / low flow coil water Δt = 6K).
(2) Entering air 20°C - supply water 35°C (Δt = 5K).
(3) Entering air 20°C - supply water 82°C (Δt = 11K).
(4) Fan gain / Fan power input based upon fan operating with design airflow at 0Pa ESP, these values may change with
different airflows and ESPs.
(5) Machine weight excludes water volume.
(6) Pressure drop includes pressure independent control valve, coil, changeover valves and pipework.
(7) Unit running at nominal conditions.
(8) Nominal motor running load is at design airflow of 140l/s.
Comfort