Condensate Drain
During operation in cooling mode, the unit removes moisture and lowers humidity from the air. This moisture must be
removed to ensure that the drain tray does not overflow.
The condensate pump outlet must be connected to the building drainage system as per the diagram below.
6mm ID braided hose is recommended for the condensate drain hose. Ensure that the hose is not damaged or kinked
during installation. The hose is required to have a fall of 1/50 to 1/100. The fall, provision of air gaps (tundish) or water
traps, and connection to appropriate drainage should follow local design code.
Max 800mm
Gradient 1/50 -1/100 Fall
ARTUS™
Comfort